If viewed as a single large screen, the layout is as follows:
The Month and Day entries select the month (1 to 12) and
day (1 to 31) of the holiday. The time settings are in 24-hour
time, with Start Time used to set the time of day to start of the
holiday. The End Time line is used to set the end of the holiday.
The NEXT item at the bottom of screen moves you to the next
holiday schedule set point.
Setting the month or day or start time and end time to 0 dis-
ables the holiday schedule.
The holiday schedule cancels any normal schedule set for
the holiday date and time. If a normal schedule is set from 0700
to 1800 hours and a holiday schedule is set for the same day
from 0800 to 1700, the unit will be unoccupied from midnight
to 0700. The unit will change to occupied mode at 0700 until
0800. At 0800 the holiday schedule forces the unit to
unoccupied mode until 1700. At 1700, control returns to the
normal schedule and the unit goes occupied from 1700 to
1800. At 1800, the unit returns to unoccupied mode per the
normal schedule.
OVERRIDE SCHEDULES
1. From the HOME menu, select the [CONFIG] softkey
to enter the CONFIGURATION menu.
2. Use the arrow keys to select OCCUPANCY, then press
<ENTER>.
3. Press the [OVERRIDE] softkey to adjust the override
schedules.
4. Use arrow keys to scroll around the screen and select the
data field to change. These buttons scroll through the data
fields, as well as up and down the screen.
5. To change a field, move the cursor brackets to the desired
field then press <ENTER>.
6. If the wrong field is entered or you do not want to change
a value, press [CANCEL] to leave the current setting in-
tact.
7. Press the [PREV] softkey to move the previous screen or
schedule. Press the [NEXT] softkey to move to the next
schedule screen.
If viewed as a single large screen, the layout is as follows:
The Month and Day entries select the month (1 to 12) and
day (1 to 31) of the override. The time settings are in 24-hour
time, with Start Time used to set the time of day to start of the
override. The End Time line is used to set the end of the over-
ride. The NEXT item at the bottom of screen moves you to the
next override schedule set point.
Setting the month or day or start time and end time to 0 dis-
ables the override schedule.
The override schedule has the highest priority of any sched-
ule. When an override schedule is active, it overrides any nor-
mal or holiday schedule and forces the unit to occupied mode.
In the example listed under the holiday schedule, assume an
override schedule is set for 1300 to 1400 of that day. The unit
operation remains the same, except the unit will switch to oc-
cupied mode from 1300 to 1400.
Adjust Set Points —
The user must be logged on as
User or Admin to configure set points.
1. From the HOME menu, select the [CONFIG] softkey
to enter the CONFIGURATION menu.
2. Use the arrow keys to select SETPOINT, then press
<ENTER>.
3. Use arrow keys to scroll around the screen and select the
data field to change. These buttons scroll through the data
fields, as well as up and down the screen.
4. To change a field, move the cursor brackets to the desired
field then press <ENTER>.
5. If the wrong field is entered or you do not want to change
a value, press [CANCEL] to leave the current setting
intact.
See Table 3 for a description of the items on the SETPOINT
menu.
Table 3 — Setpoint Menu
LEGEND
--------------------- Holiday Schedule #1 ---------------------
Mont
h
:
0
Day :
0
Start Time
[hh:mm]
0:
0
End Time
[hh:mm]
0:
0
[->PREV]
[->NEXT]
[->HOME]
--------------------- Override Schedule #1 ---------------------
Mont
h
:
0
Day :
0
Start Time
[hh:mm]
0:
0
End Time
[hh:mm]
0:
0
[->PREV]
[->NEXT]
[->HOME]
SET POINT
DEFAULT
RANGE
Duct Static Pressure (VAV Setpoint)
1.5 in. wg
0.05 to 3 in. wg
Supply Fan Proof Level (Fan On)
0.4 in. wg
0 to 0.5 in. wg
Occupied Cooling (Space)
74 F
(Occupied H1) to
100 F
Occupied Heating (Space)
70 F
0 to (Occupied Cooling -
1) F
Unoccupied Cooling (Space)
85 F
(Unoccupied H1)
to 100 F
Unoccupied Heating (Space)
55 F
0 to (Unoccupied Cool-
ing -1) F
Supply Air Cooling
55 F
50 to 70 F
Supply Air Heating
120 F
(Cooling Set point + 10)
to 140 F
Supply Air Reset Ratio
3.0 F
1 to 10 F
Maximum Supply Air Reset
20 F
0 to 20 F
Refrig. Head Pressure
225 psig
200 to 300 psig
Economizer Lockout (Air Econ)
68 F
50 to 85 F
Air Econ Minimum Position
20%
0 to 100%
Indoor Air Quality
850 ppm
0 to 2000 ppm
Occupied Humidify
0% rh
0 to Occupied Dehumid-
ify % rh
Occupied Dehumidify
100% rh
Occupied Humidify to
100% rh
Unoccupied Humidify
0% rh
0 to Unoccupied Dehu-
midify% rh
Unoccupied Dehumidify
100% rh
Unoccupied Humidify to
100% rh
Space Static Pressure
0.02 in. wg
0 to 0.3 in. wg
Space Static Sensor-Low
-0.5 in. wg
-1 to -0.2 in. wg
Space Static Sensor-RNG (range)
1 in. wg
0 to 2 in. wg
H2O Econ Flush Duration
12 min
3 to 20 minutes
H2O Econ Flush Interval
12 hrs
12 to 168 hours
T55 Time Override Hours
1 hour
0 to 24 hours
ppm
—
Parts Per Million
rh
—
Relative Humidity
VAV
—
Variable Air Volume