![background image](http://html.mh-extra.com/html/carrier/graviner-mk6/graviner-mk6_installation-operation-and-maintenance-manual_2563924056.webp)
Nov-21
Page 56 of 132
59812-K001 Rev 10
2.8.7
Deviation Alarm
Have the Maximum actual level for each engine to hand as used in setting the Average alarm level
(from step 4. in section 2.8.6 above).
Enter MAIN MENU and select ENGINEER MAIN MENU. Enter the password, Press
1.
Enter the System Status menu, Figure 51, and select 2. Detector.
Figure 56
Detector Status Menu
2.
Select 2. Detector Status,
Figure 57
Detector Status Engine Selection
3.
Select the required Engine from the list.
Figure 58
Detector Status Detector Selection
4.
Select the required Detector from the list.
Figure 59
Detector Status
5.
Read the Peak Level on each Detector. Subtract the Maximum actual level for that engine
from each of the Detector peak levels and multiply each result x 2. This becomes the
deviation alarm level entered into the Control Panel.
Summary of Contents for Graviner Mk6
Page 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Page 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Page 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Page 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Page 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Page 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Page 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Page 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...