Figure 48
Clear Peak and Average Values
Select YES and press
2.
Clear the maximum average reading for each engine to ensure all test readings are erased.
This can be done via MAIN MENU: ENGINEER 1. Configure System 7. Clr Max Average.
Figure 49
Clear Maximum Average Values
Select the required engine and press
Figure 50
Confirm Clear Maximum Average Values
Select YES and press
The above should be carried out for all engines being monitored. This should also be carried out after
any smoke testing.
2.8.6
Average Alarm
1.
Enter the Main Menu: Engineer, Figure 41, and select 2. System Status.
Figure 51
System Status Menu
2.
Select 1. Engine
Summary of Contents for Graviner Mk6