
Nov-21
Page 34 of 132
59812-K001 Rev 10
2.6
CONNECTING THE SYSTEM
2.6.1
Input power
+24 V dc and 0 V dc power input cables for the Control Panel should be terminated onto Interface Board
Supply Input (terminal block TB5).
Where required by the vessel approval authority two separate 24v supply cables may be necessary. The
two cables should be routed by different paths to reduce the risk of damage affecting both cables.
Cables should be segregated from high voltage cables and follow good installation practice
Note all terminations should be made using crimped wires.
For each of the power connections strip the power cable to the required length to connect to the
terminals in the Control Panel. Then remove approximately 1cm of the outer sheath to expose the cable
screen as shown below.
Figure 17
Power cable
Feed the cable into the Control Panel via a metal IP65 EMC gland supplied, ensuring that the
metal prongs make a good contact with the exposed cable screen as shown below. The gland
should be fixed in place using a toothed nut to cut through the Control Panel paint.
Exposed screen
Summary of Contents for Graviner Mk6
Page 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Page 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Page 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Page 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Page 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Page 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Page 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Page 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...