59812-K001 Rev 10
2.9.4
Detector Smoke Alarm Test
A smoke test should be performed on each detector to ensure that the correct response is obtained.
One of two methods may be used to conduct the Smoke Alarm Test.
Note: Isolation of the Slowdown/Shutdown relays is required before commencing the smoke
alarm test, see sections Error! Reference source not found. and Error! Reference source not found.. If
the Common Alarm Relay is connected to the engine slowdown or shutdown system this should
be disconnected.
Warning: Carrying out this test without isolation or disconnection of the output relays will cause
the engine slowdown or shutdown system to operate.
Method 1 Using a Wick
1.
Cut a length of wick approximately 30 mm long. Assemble the smoke tester by pushing the
wick into the wick holder fitted with the pipette bulb. Press the nylon pipe into the Pipe
connector (refer to Error! Reference source not found.).
Figure 69
Smoke Tester
2.
Push the nylon pipe of the smoke tester into the connector on the side of the Detector base
body (refer to Error! Reference source not found.).
Summary of Contents for Graviner Mk6
Page 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Page 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Page 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Page 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Page 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Page 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Page 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Page 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...