Nov-21
Page 55 of 132
59812-K001 Rev 10
Figure 52
Engine Status Selection
3.
Select the required Engine (1 2, 3, 4, etc) from the list.
Figure 53
Engine Status
4.
Read Maximum actual level value (retain this value for deviation alarm setting).
5.
Set Average alarm level to twice the Maximum actual level, as follows:
Return to the Configuration menu, Figure 42 select 3, Alarm Levels,
Figure 54
Set Alarm Levels
Select 1. Set Average Alarm.
Figure 55
Set Engine Average Alarm
Select engine number, press
Enter the new alarm level in the range 0.3 to 1.3mg/l as
calculated from above. If the calculated value is outside these limits set the alarm level to
the nearest value in the range.
6.
Repeat steps 1 to 5 for all engines.