2.6.4
Junction Box to Detector Connections
At the Junction Box strip the Detector cables to the required length. The cables should be long enough
to reach easily from the gland to the terminals. Remove approximately 1cm of the outer sheath to expose
the cable screen as shown below
Figure 30
Detector cable, stripped.
Feed the cable through a metal EMC gland, e.g. Lapp Kabel Skintop MS-SC-M-XL range, ensuring that
the metal prongs make contact with the exposed cable screen as shown below
Figure 31
Detector cable, EMC Gland assembly
Connect the cable via the relevant Detector position hole in the Junction Box.
Figure 32
Detector cable, EMC Gland & Junction Box
Connect the wires into the Junction Box terminals as detailed in the table below and tighten the gland.