Using installer settings
Carrier Connect™ Wi
-Fi Thermostat 33CONNECTSTAT43FX
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
31
Setting
Default/Range
SMART RECOVERY
—
Transitions the conditioned space from one programmable
temperature period to the next with 1°F increments of the heating setpoint or 1°F
decrements of the cooling setpoint, so that by the time the next period starts, the
setpoints are at the desired temperature. The purpose of the gradual transition is to use
less energy by preventing staging up (because of a higher demand) to higher stages. The
transitions occur in a linear fashion over the smart recovery time period.
•
If you start a temporary hold in the middle of a smart recovery, the setpoints of the
temporary hold are used.
•
If a temporary hold is already active during the time that smart recovery would have
been started, a smart recovery does not start.
If the temporary hold ends in the middle of what would have been a smart recovery, the
smart recovery starts where it would have been in the linear progression at the same
time as when the temporary hold was not active.
NOTE
The smart recovery setting is only available if the thermostat is configured as a
programmable thermostat.
D:
R:
30
NO
30 minutes
60 minutes
90 minutes
FAN ON WITH W
—
Sets the fan to turn on with any
W
output when the fan is set to
AUTO
.
Range
•
YES
- The
G
output is turned on by the thermostat when the
W1
or
W2
outputs are
energized.
•
NO
- The
G
output is not turned on by the thermostat when the
W1
or
W2
outputs
are energized.
D:
R:
YES
YES
NO
REVERSING VALVE
—
Defines whether the
ON
state of the reversing valve (
O/B
) is used
for heat pump heating or heat pump cooling if
OUTDOOR EQUIPMENT TYPE
is set to
HP
.
•
When the
ON
state of the reversing valve is used for cooling, the signal is typically
referred to as a
O
.
•
When the
ON
state of the reversing valve is used for heating, the signal is typically
referred to as a
B
demand.
R:
HEAT
COOL
SPACE TEMP OFFSET
—
Sets an offset to the displayed space temperature, which gives
the end user the convenience of matching the actual sensed temperature to a different
perceived temperature or a different temperature measuring device.
D:
R:
OFF
-5 to - 1
OFF
1 to 5°F
-2.7 to - 0.5
OFF
0.5 to 2.7°C