Using the menu for advanced features
Carrier Connect™ Wi
-Fi Thermostat 33CONNECTSTAT43FX
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
22
To adjust occupancy settings
Setting
Default/Range
SET OCC FAN
—
Operates the fan in
AUTO
or
ON
during occupied periods
NOTE
If the installer configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
REMINDER!
The
AUTO
setting is a violation of ASHRAE 90.1 and Title 24 but is a
feature of the thermostat for building owners that mandate auto fan operation during
occupied periods for energy conservation purposes.
D:
R:
AUTO
AUTO
ON
SET UNOC FAN
—
Operates the fan in
AUTO
or
ON
during unoccupied periods
NOTE
If the installer has configured the thermostat for non-programmable operation
and remote occupancy is disabled, this setting is not available.
D:
R:
AUTO
AUTO
ON
UNOCC COOL
—
The cool setpoint during unoccupied periods
NOTES
•
The minimum value you can set is limited by the unoccupied heat setpoint (cool
setpoint cannot be less than the heat setpoint) and the installer setting for
MIN
COOL SETPOINT
.
•
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
D:
R:
85°F
52 to 90°F
UNOCC HEAT
—
The heat setpoint during unoccupied periods
NOTES
•
The maximum value is limited by the unoccupied cool setpoint (heat setpoint cannot
be greater than the cool setpoint) and the installer setting for
MAX HEAT SETPOINT
.
•
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
D:
R:
62°F
50 to 88°F
OCC COOL
—
The cool setpoint during occupied periods
NOTES
•
The minimum value is limited by the occupied heat setpoint (cool setpoint cannot
be less than the heat setpoint) and the installer setting for
MIN COOL SETPOINT
.
•
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
D:
R:
75°F
52 to 90°F
OCC HEAT
—
The heat setpoint during occupied periods
NOTES
•
The maximum value is limited by the occupied cool setpoint (heat setpoint cannot
be greater than the cool setpoint) and the installer setting for
MAX HEAT SETPOINT
.
•
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
D:
R:
70°F
50 to 88°F