Setting
Default/Range
TIME BETWEEN FUEL TYPES (ELECTRIC TO GAS)
—
Sets a minimum amount of time that
the system runs on compressor heat before transitioning to the furnace.
Range - The minimum number of minutes the compressor is energized to satisfy a
heating demand before transitioning to gas heat.
NOTES
•
This selection is only available if the
HEATING EQUIPMENT
is set to
GAS
and the
COMPRESSOR
is set to
HP
.
•
The minimum number of minutes the compressor runs in heating before staging up
to gas heat is the larger of this setting and the
STAGE DELAY
setting.
D:
R:
15 minutes
10, 15, 20, 25 minutes
CYCLES PER HOUR
—
Sets a maximum number of equipment cycles per hour. Based on
selecting 2, 4, 6 or 8 cycles per hour, this timer is set to 30, 15, 10 or 8 minutes. This
time must elapse from the start of one cycle before another cycle can start.
The Range - The maximum number of times the equipment can turn on per hour.
NOTE
When the equipment is off and the user changes the setpoint to create a heating
or cooling demand, the cycles per hour requirement is ignored to provide a timely
response to the user’s request. The
cycles per hour limitation become active again when
the
Y1
,
Y2
,
W1
or
W2
outputs transition from
ON
to
OFF
.
D:
R:
4
2, 4, 6, or 8
MAX HEAT SETPOINT
—
Sets a maximum heating setpoint. This is the maximum heat
setpoint value that can be used in the program schedule or when the user adjusts the
setpoint to temporarily override the program schedule.
NOTE
This setting is not available if
HEATING EQUIPMENT
is set to
NONE
. (
HEAT EQUIP
=
ELEC
and
HEAT STAGES
=
0
)
D:
R:
88°F
50°
–
88°F
(1°F increments)
MIN COOL SETPOINT
—
Sets a minimum cooling setpoint that can be used in the program
schedule or when the user adjusts the setpoint to temporarily override the program
schedule.
NOTE
This setting is not available if the
COMPRESSOR
is set to
NONE
.
D:
R:
52°F
52
–
90 °F
(1°F increments)