Using installer settings
Carrier Connect™ Wi
-Fi Thermostat 33CONNECTSTAT43FX
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
42
Setting
Default/Range
DEVICE NAME
This setting can be viewed but not modified from the display. The
DEVICE
NAME
can be
updated over BACnet when the
BACNET CONFIG WRITE
is set to
YES
.
Device Object Names on BACnet devices must not only be unique on MS/TP segment
like the MAC address, but must also be unique internetwork-wide.
The top line in this screen scrolls to display
DEVICE NAME
and the name.
NOTE Changing the Device Object Name causes the Database Revision property of the
Device to be incremented.
This setting is not be displayed if BACnet is disabled.
D:
R:
DEVICE 16xxxx (last 4
digits of the serial number)
Any printable string with a
maximum length of 16
characters
DEVICE LOCATION
—
To view, but not modify from the display, the Device Location, which
is an optional property used to describe the physical location of the BACnet device.
The
DEVICE LOCATION
can be updated over BACnet when the
BACNET CONFIG WRITE
configuration is set to
YES
.
The top line in this screen scrolls to display the
DEVICE LOC
and the location.
This setting is not displayed if BACnet is disabled.
D:
R:
LOCATION
The display is limited to
showing only the first 28
characters of the
maximum 32 characters
allowed.
DEVICE DESCRIPTION
—
To view, but not modify from the display, the Device Description.
Description is an optional property used to add descriptive information about the BACnet
device.
The Device Description can be updated over BACnet when the
BACNET CONFIG WRITE
configuration is set to
YES
.
The top line in this screen scrolls to display the
DEVICE DES
and the description.
NOTE This setting is not displayed if BACnet is disabled.
D:
R:
DESCRIPTION
The display is limited to
showing only the first 28
characters of the
maximum 32 characters
allowed.
BACnet BMS OCC
—
Enable or disable occupancy scheduling through the BACnet BMS by
enabling or disabling the connection between the Present Value of the BACnet Binary
Object Value named
BMS_OCC
and the occupancy state of the controller.
NOTE
Occupancy is determined using 1 of 3 methods.
BACnet BMS OCC
is mutually
exclusive with both
PROGRAMMABLE MODE
and
REMOTE SENSOR
set to
OCCUPANCY
.
Setting
BACnet BMS OCC
to
Yes
forces
PROG
or
NON-PROG
to
NON-PROG
and switches
REMOTE SENSOR
to
None
if set to
OCCUPANCY
.
This setting is not displayed if BACnet is disabled.
D:
R:
YES (enabled)
YES (enabled)
NO (disabled)
BACNET CONFIG WRITE
—
Allow (
YES
) or disallow (
NO
) BACnet writes to modify system
settings. Many of the configuration items are exposed as BACnet objects. These BACnet
objects can be read to verify the thermostat's configuration. If
BACnet Config Write
is set
to
YES
, these objects can also be written to change the thermostat's configuration. If set
to
NO
, these objects are read-only.
NOTE
This setting is not displayed if BACnet is
disabled.
D:
R:
YES
YES
NO
NET GP OUT TIMEOUT
—
Set the timeout associated within network general purpose
outputs. If this value is set to 2 minutes, 20 minutes, or 60 minutes, this number
represents the maximum time that can lapse between writes to the Present Value
property of the output object before the value returns to the inactive state.
NOTE
This setting is not displayed if BACnet is disabled.
D:
R:
2 minutes
2
–
2 minutes
20
–
20 minutes
60
–
60 minutes
UNLM - Unlimited