47
114°F
11 .10
Access to the INFO menu
Make sure you are in the “Operation mode”, backlight ON (see
section 11.6).
Using the boiler control panel it is possible to access the INFO
menu by pressing the “MENU/RESET” button one to illuminate the
screen, then again for less than 5 seconds. The INFO menu allows
the user to view some of the boilers sensor readings and can be
very helpful when diagnosing issues with the unit (see INFO list in
the next column; indexed by a lower case alphabetical letter).
Pressing the “MENU/RESET” button for more than 5 seconds will
access the Parameter menu.
This menu will timeout with inactivity in about 30 seconds if
accidental accessed.
136°F
Once the button is pressed, the first value of the INFO menu
appears: e. g. “a130.6°F”. It scrolls from right to left because of the
length of the string (up to 5 characters) in the following sequence:
value + unit of measure.
a130.
To move from one letter to another press the “MODE/OK” button.
The next value will appear: e. g. “b135.1°F” (sliding from right to left).
b135.
INFO list
INFORMATION
STRING
CH sensor
“a” + “value (e.g. xx.x)” + “°F”
Return sensor
“b” + “value (e.g. xx.x)” + “°F”
DHW sensor
“c” + “value (e.g. xx.x)” + “°F”
Flue sensor
“d” + “value (e.g. xx.x)” + “°F”
Outdoor temperature
sensor
“e” + “value (e.g. xx.x)” + “°F”
Fan speed
“f” + “value (e.g. xxxx)” + “rpm”
Flue hour counter
“g” + “value” + “h”
CH Water Pressure
“h” + “value” + “psi”
Domestic Flow Rate
“i” + “value” + “gpm”
Boiler firmware version
"j" + “version”
Past days since service
required
“k” + “number of days” + “days”
11 .11
Access to the PARAMETER menu
NOTICE: Make sure you are in the “Operation mode”, backlight
ON (see section 11.6).
Access to the PROGRAMMING menu by pressing the “MENU/
RESET” button for at least 5 seconds, until “000” appears.
Pressing the “MENU/RESET” button for less than 5 seconds will
access the
INFO
menu.
136°F
The display shows ”000”.
000
Now you can enter the password menu. The password to access
the installer level is “018”, service level is “053”.
9
WARNING:
The parameters accessed by using this parameter
should only be adjusted by a qualified service technician.
Failure to comply may result in substantial property damage,
severe personal injury or death.
To set the password turn either knob clockwise to increase in value
and counterclockwise to decrease in value. Once at “018” (or 053),
confirm the password pressing the “MODE/OK” button.
018
The first parameter of the list will appear on the display: the string
can be fixed or sliding (if the text exceeds 5 characters, e. g. GAS
TYPE).
It is possible to navigate through the menu by rotating one of the
two knobs: clockwise or counterclockwise.
GAS T
Select the parameter by pressing the “MODE/OK” button.