![Carrier BWCAAG000120 Installation & Operating Instructions Manual Download Page 31](http://html.mh-extra.com/html/carrier/bwcaag000120/bwcaag000120_installation-and-operating-instructions-manual_2562170031.webp)
31
I
Clearance to service regulator vent outlet
3 ft. (0.9m)
3 ft. (0.9m)
J
Clearance to non-mechanical air supply inlet
12" (305mm)
3 ft. (0.9m)
K
Clearance to mechanical air supply inlet
3 ft. (0.9m) above if within
10 ft. (3m) horizontally
L
Clearance above paved sidewalk or paved driveway located on public
property
5
7 ft. (2.1m)†
7 ft. (2.1m)†
M
Clearance under veranda, porch, deck or balcony
12" (305mm)‡
12" (305mm)‡
N
Clearance to the combustion air inlet to any other appliance
12" (305mm)
3 ft. (0.9m)
Notes:
1 - Canadian installations must comply with the current CSA B149.1 Natural Gas and Propane Installation Code and local building codes.
2 - US installations must comply with current ANSI Z223.1/NFPA 54 National Fuel Gas Code and local building codes.
3 - Concentric vent must protrude from the roof 24” (610mm) measuring from the terminalend-cap vanes.
4 - 24” is the recommended snow level allowance above grade/roofline or any surface that will support snow, debris, or ice (i.e. for roof venting
clearances - roofline and snow level). If living in a snowfall region, consult your local weather office for the maximum typical snowfall for
your area.
5 - Above public walkways, driveways or parking lots if adjacent to it and condensate cannot drip, freeze, or create a hazard.
6 - The termination shall be located, or protected by a guard, in such a way to prevent possible contact.
† - A vent shall not terminate directly above a sidewalk or paved driveway that is located between two sinlge family dwellings and serves both
dwellings.
‡ - Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
9
WARNING:
Vent termination must keep the following minimum clearances from electric meters, gas meters, regulators and relief
equipment: 4 ft. (1220mm) horizontally and in no case above and below, unless a horizontal distance of 4 ft. (1220mm) is maintained.
Ter
mination Clearance Quick Reference Diagram