28
Existing Chimney Chase Way
Chimney
Cap
Existing
Exhaust Vent
Chimney
(used as a
chase way)
Air-Inlet
Exhaust Vent Min.
18 in. above air-inlet
Min. 12 in. above
Air-Inlet
roof and snow level
It is permissible to use an existing chimney as a chase way to run
the Vent/Air-inlet piping as long as:
1. The chimney is not being used by any other appliance.
2. Flue gases do not enter the vacant chimney.
3. Only approved vent manufacturer’s venting shown in section
8.9 can be used.
Vent lengths are within the maximums specified.
4. The top of the chimney is capped and the Vent Air-inlet pipes
are flashed to prevent leakage into the vacant chimney.
Under no circumstances may an existing chimney or chase-way
be used to vent or provide combustion intake air to the boiler. The
existing chimney or chaseway can only be used as a passageway
to allow the approved venting material to pass through. Failure to
follow these instructions will result in fire, property damage, serious
injury or death.
8 .5
Combustion Air and Ventilation Openings
Provisions for combustion and ventilation air must be made in
accordance with section 5.3, Air for Combustion and Ventilation, of
the National Flue Gas Code, ANSI Z223.1/NFPA 54, or Sections
7.2, 7.3 or 7.4 of CAN/CGA B149.1, Installation Codes, or
applicable provisions of the local building codes.
9
CAUTION: BOILER DAMAGE AND OPERATIONAL
FAILURES!
Provisions for combustion air and ventilation are always requi-
red through a grille, regardless whether the combustion air is
taken from the outside (sealed combustion).
9
Make sure that intake and exhaust openings are sufficiently
sized and no reduction or closure of openings takes place
− If this is not the case, then the problem is not resolved, do not
operate the boiler.
− Please note these restrictions and its dangers to the operator
of the boiler.
9
WARNING: BOILER DAMAGE!
− Boiler must be clear and free from combustible materials,
gasoline and other flammable vapors and liquids, and corrosive
liquids and vapors. Never use chlorine and hydrocarbon
containing chemicals (such as spray chemicals, solution and
cleaning agents, paints, glues etc.) in the vicinity of the boiler
.
− Do not store and use these chemicals in the boiler room
.
− Avoid excessive dust formation and build-up
.
9
DANGER: FIRE DANGER!
−
Do
not store flammable materials and liquids in the immediate
vicinity of the boiler
.