![Carrier BWCAAG000120 Installation & Operating Instructions Manual Download Page 58](http://html.mh-extra.com/html/carrier/bwcaag000120/bwcaag000120_installation-and-operating-instructions-manual_2562170058.webp)
58
9
WARNING:
DO NOT rinse the insulation panel.
9
NOTICE:
In case of serious dirt build-up rinsing can be
repeated several times, spray white vinegar and wait about 3
to 5 minutes, clean with a mechanical nylon brush and rinse
with mains water.
9
WARNING:
DO NOT spray and rinse the insulation panel.
−
MANDATORY:
Check the insulation panel and, if it is worn, it
must be replaced
9
WARNING:
Material characteristics do not require individual
protection devices but, for safety, we recommend the use of a
protective mask, gloves and glasses.
9
WARNING:
During operations, protect the lower part of the
internal coils of the heat exchanger to avoid that dust and parts
of the insulation panel fall off within them.
To replace the insulation
−
Use a blade to cut the insulation panel approximately 2,63” (60
mm) from the circumference.
−
Lift and remove the 2 panel pieces from the seat.
NOTICE:
The insulation panel is fixed by a central clip and six radial
clips; if during removal operations the clips detach, remove them
from the combustion chamber.
−
Vacuum any material residue present on the exchanger coils
and panel support.
−
Position the new insulation panel close its seat and insert it
completely by pressing on central part.
−
MANDATORY:
Check the flue outlet gasket and, if it is worn, it
must be replaced.
−
Reassemble the burner door set on the heat exchanger
respecting a tightening torque of the four nuts at 5Nm.