Fig. 1
Horizontal flue terminal 2/4 in. (ø 60-100 mm) PP flue
gases/air
BWCAAG000120
BWHAAG000120
BWCAAG000150
BWHAAG000150
Max length (L)
30 ft (9.14 m)
23 ft (7.01 m)
Terminal length (L1)
2.33 ft (0.711 m)
2.33 ft (0.711 m)
It
is mandatory to use the Ø 2” (60 mm) vent adapter (see “4.2 Boiler box content”
page 5), factory supplied and approved with the boiler, for venting connection
Vent adaptor
Ø 2 (60 mm)
(factory supplied)
fig. 1
Fig. 2
Vertical flue terminal 2/4 in. (
Ø
60-100 mm) PP flue
gases/air for pitched roof
BWCAAG000120
BWHAAG000120
BWCAAG000150
BWHAAG000150
Max length (L)
35 ft (10.67 m)
28 ft (8.53 m)
Terminal length (L1)
4.17 ft (1.27 m)
4.17 ft (1.27 m)
Vent adaptor Ø 60 mm
(factory supplied)
fig. 2
Fig. 3
Vertical flue terminal 2/4 in. (
Ø
60-100 mm) PP flue
gases/air for flat roof
BWCAAG000120
BWHAAG000120
BWCAAG000150
BWHAAG000150
Max length (L)
35 ft (10.67 m)
28 ft (8.53 m)
Terminal length (L1)
4.17 ft (1.27 m)
4.17 ft (1.27 m)
fig. 3
Vent adaptor Ø 60 mm
(factory supplied)
Fig. 4
Horizontal flue terminal 3/5 in. (
Ø
80-125 mm) PP flue
gases/air
BWCAAG000120
BWHAAG000120
BWCAAG000150
BWHAAG000150
Max length (L)
40 ft (12.19 m)
60 ft (18.29 m)
Terminal length (L1)
2.42ft (0,74 m)
2.42ft (0,74 m)
increaser 2”-3”
fig. 4
V
ent adaptor Ø 3”
80 mm
(factory supplied)
It is mandatory to use the Ø 3” (80 mm) vent adapter (see “4.2 Boiler box content”
page 5), factory supplied and approved with the boiler, for venting connection