CL-5
Unit Control Configuration
(
Home
Setup
Unit Config
)
Configured the Zone Sensor Option, Push-Button Override, and Zone Setpoint Adjust based on the ZAT sensor
operation from the SAT Reset or NSB sections of the pre-startup checklist (if needed)
Adjust the Setpoint /- set point based on the max set point adjustment from the SAT Reset or NSB sections
of the pre-startup checklist (if required)
Verify the NSB Option is set to “None” for units without the night setback ETO or indicate the type of operation
that’s needed from the NSB operation section of the pre-startup checklist (if required)
Verify the Misc Options A is configured for clogged filter indicator (CFI) and condensate overflow switch (COS) for
units without a factory or field installed smoke detector (SD) or configured for CFI, COS, SD for units with a factory or
field installed smoke detector
Verify the Misc Options B is configured for either “None”, “S/S Switch” (start/stop switch), “EMSD” (emergency
shutdown), or “EMR” (energy management relay) as indicated in the occupancy or shutdown control sections of the
pre-startup checklist
SAT Reset (if equipped)
(
Home
Setup
SAT Reset
)
Adjust the ZAT ratio as needed (default is 1°F). Increase the ratio reduce the reset amount
Adjust the SAT ratio as needed (default is 3°F). Increase the ratio to increase the reset amount
Adjust the Max Change as needed (default is 15°F)
Adjust the Clg ZAT SP to match the design occupied cooling zone air temperature from the SAT reset section of
the pre-startup checklist
Adjust the Htg ZAT SP to match the design occupied heating zone air temperature from the SAT reset section of
the pre-startup checklist
DPT Summary (if equipped)
(
Home
Setup
DPT
)
Review the range for the duct pressure transmitter (if exists). Enter the range minimum for the SF-DPT Minimum
and the range maximum for the SF-DPT Maximum.
Review the range for the space pressure transmitter (if exists). Enter the range minimum for the Zn-DPT Minimum
and the range maximum for the Zn-DPT Maximum.
Manual Override
(
Home
Setup
Man Ovrd
)
Verify all manual override outputs are set to “Off” (unless supply and exhaust fan values have been set by air
balance contractor)
Calibration
(
Home
Setup
Calibration
)
Verify all offsets are set to “0.00” (unless adjustments have been made by a professional calibrator)
Set Time and Date
(
Home
Setup
Misc. Settings
BAS Setup
Set Time and Date
)
The current time and date has been set in the controller
Equipment Configuration
Tech Settings
Parameter
Configuration
Parameter
Configuration
SF Option
Occupancy Control
EF Option
Manual Occ Control
HGRH Option
Enable Operation
Dehum Option
Emergency Shutdown
Heating Option
Emergency Heat
Cooling Enabled By
Supply Fan Min %
Heating Enabled By
Supply Fan Min HP
Temp Option #1
ZAT Reset
Temp Option #2
Ht Water Vlv Min %
Humidity Option #1
SF Occ/Unocc
Humidity Option #2
Air Pressure Option