background image

CSRN-XHE2 

49.4-110.4 

R-410A

M07V40B13

07

   

11/20

 

MANU

AL

 

FO

R

 

INS

TALLA

TIO

N,

 

USE

 

AND

 

MAINTENANCE

Summary of Contents for CSRN-XHE2 Series

Page 1: ...CSRN XHE2 49 4 110 4 R 410A M07V40B13 07 11 20 MANUAL FOR INSTALLATION USE AND MAINTENANCE...

Page 2: ...ime with highly reliable efficient high quality and safe solutions The target of the company is to offer advanced systems that assure the best comfort and reduce energy consumption as well as the inst...

Page 3: ...Con gurations 7 Reception 10 Selecting the installation site 12 Water connections 17 Aeraulic connections 20 Electrical connections 21 Start up 28 Control 36 Maintenance 60 Decommissioning 67 Residua...

Page 4: ...se damages to things and injuries people Intended use Use the unit only civil air conditioning keep to the limits foreseen in the technical schedule and in this manual The manufacturer accepts no resp...

Page 5: ...vements may imply manual data changes Visit manufacturer web site for updated data Indications for the User Keep this manual with the wiring diagram in an accessible place for the operator Note the un...

Page 6: ...refrigerant charge manufacturer logo and address The matriculation plate must never be removed It contains fluorinated greenhouse gases Serial number It identifies uniquely each unit Must be quoted wh...

Page 7: ...air S Supply air FA Fresh air 1 G4 efficiency filters electronic filters option or F7 filter option 2 Handling exchanger 3 Supply fan section 4 Hot gas reheating exchanger 5 Electric heaters 6 Thermod...

Page 8: ...ger 5 Electric heaters 6 Thermodynamic recovery on exhaust air 7 Exhaust damper 8 Exhaust fan section 9 Thermodynamic recovery on exhaust air R Return air S Supply air FA Fresh air EX Exhaust air 1 G4...

Page 9: ...stage standard G4 ISO 16890 Coarse 60 2 filtering stage option F7 ISO 16890 ePM1 55 2 filtering stage option FES electronic filters ISO 16890 ePM1 90 Filters nomenclature according to EN ISO 16890 Sta...

Page 10: ...damage you found and quote this sentence Conditional acceptance clear evidence of deficiencies damages during transport wontact by fax and registered mail with advice of receipt to supplier and the c...

Page 11: ...to guarantee the safety of the personnel present and the of material Verify unit weight and handling equipment lifting capacity Identify critical points during handling disconnected routes flights st...

Page 12: ...e any leaking gas cannot enter buildings or stagnate in closed areas In the latter case observe the rules for machinery rooms ventilation leak detection etc Installation standards install the unit rai...

Page 13: ...Avoid the accumulations of snow and ice in front of the exhaust air outlet Pressure relief valve gas side The installer is responsible for evaluating the opportunity of installing drain pipes in compl...

Page 14: ...n the specific installation requirements the length of the chimney can be increased with suitable joints and fittings not supplied by Clivet Gas connection Read the gas heating module manual Connectio...

Page 15: ...ce of air bypass A Apply the flat adhesive gasket15x5 on the Gas Module flange perimeter to guarantee the absence of air bypass B Fix with screws the flue supporting bracket to the GM frontal panel C...

Page 16: ...16 Gas use features Connections performed by costumer A rooftop B supply fan C gas module D connecting cables E electrical panel terminal XG...

Page 17: ...pings Connect the condensate discharge to a sewerage drainage network DO NOT use white water or drainage networks to avoid the aspiration of odours in the case of evaporation of water contained in the...

Page 18: ...ater Respect the limits indicated in the table No relation can be demonstrated between water hardness and conductivity Limit values for the supply water conductivity medium low medium high min max min...

Page 19: ...19 Heating coil Option Max operating pressure 10 bar A drain cock B vent valve Provided by the costumer 1 anti vibration devices 2 piping supports 3 Shut off valves 1 3 A B 2...

Page 20: ...portunity of equipping them with deflectors in particular with high air speed or bends with reduced radius Treated air channelling The internal surface of the channel must be smooth enable its washing...

Page 21: ...admitted conditions F L I full load input full load power input at max admissible condition Electrical wiring diagram Nr Connections refer to the unit electrical diagram the number of the diagram is...

Page 22: ...Do not lay the cables parallel to other cables cable crossings are possible only if laid at 90 Connect the screen to the ground only if there aren t disturbances Guarantee the continuity of the scree...

Page 23: ...e only if the unit is equipped with a hot water integration coil HLC Compressor status signal lamp HLHE Warning light of the heat pump operating status HLVE Indicating light of the return and or suppl...

Page 24: ...operty Set the IP address 192 168 1 100 Set Subnet mask as 255 255 255 0 confirm OK Enter Start Windows button Write the command cmd and enter do it Write and run the command Ping 192 168 1 42 if will...

Page 25: ...ace A user interface B B1KNX bus max 350 mt twisted pair with shield 0 8 mm EIB KNX cable marking recommended C power supply unit N125 11 5WG1 125 1AB11 C1 AC 120 230 V 50 60 Hz Distance up to 350 mt...

Page 26: ...an internal terminator it must be enabled using the specific jumper dip switch or link The cable must have insulation features and non flame propagation in accordance with applicable regulations The R...

Page 27: ...software error fixed hardware error LED BUS communication with LONWORK green communication ok yellow startup flashing communicating not possible red communication down LONWORK CABLE TYPES Echelon allo...

Page 28: ...make sure no tension is present After turning off the power wait at least 5 minutes before accessing to the electrical panel or any other electrical component Before accessing check with a multimeter...

Page 29: ...any oil stains can be symptom of leaks caused by for example transport handling or other 2 Check the cooling circuit is pressurised use the machine pressure gauges if present or service pressure gauge...

Page 30: ...within in the operating limits Start up the unit With unit operating in stable conditions check Voltage Total absorption of the unit Absorption of the single electric loads Scroll compressor The Scro...

Page 31: ...erviced room are closed 2 calibration must be carried out with unit all in recirculation during the first 20 minutes from start up the unit is in full recirculation 3 set the nominal air flow range me...

Page 32: ...rved area in case it is temporarily not used which can for example occur at night The ECO mode can be activated manually from keyboard with MODE menu automatically by means the time slots automaticall...

Page 33: ...m start up the unit is in full recirculation 3 On display view the state PDiffRipresa_X4 AI 955 value of the return load losses 4 Wait for the pressure value to stabilise and take note of the value 5...

Page 34: ...n off outdoor air shutter closed overpressure shutter closed room kept in depression supply fan off ejection fan on outdoor air shutter closed overpressure shutter open supply fan on ejection fan off...

Page 35: ...rbed If enabled by signal the greater is the signal the lower is the absorbed electrical power For the connections see the wiring diagram Low set up outdoor temperature Option indicated for very cold...

Page 36: ...an example see the following Compulsory verification of the first installation only for units assembled on the installer s building site for ex Condensing circuit direct expansion unit Certification...

Page 37: ...ion are alternated every 2 seconds When the status is OFF changes to the SETPOINT and schedule are blocked Humidifier Dehumidifier mode The Humidifier mode is active If flashing it means the Dehumidif...

Page 38: ...ManSet xx C Starting from this value the module determines 2 setpoint COOLING manset dead area 2 xx 1 C HEATING manset dead area 2 xx 1 C AUTOMATIC TEMPERATURE SETPOINT The setpoint can also AUTOMATI...

Page 39: ...scription 0 SetUrCool Relative humidity setpoint in Cool mode 1 SetURHeat Relative Humidity setpoint in Heat mode 2 SetEcoCool Temperature setpoint in cool economy mode 3 SetEcoHeat Temperature setpoi...

Page 40: ...p _B3 AI 687 2 RH Return_X1 AI 955 3 RH External_X2 AI 955 4 QualityAir_X2 AI 687 5 Nr active compressors 6 ActVcInt 7 Cmd ExternalDamper_X7 AO 687 8 PowerHum Example of status codification Supply tem...

Page 41: ...ys disabled select to confirm exit 16 3 C 17 00 COD _ _ _ _ T0 ON n key key n key key T0 T5 T1 T6 T2 T7 T3 ALL All keys T4 Key code table T1 OFF ALL OFF ESC 16 3 C 17 00 DATE AND HOUR Press HOUR digit...

Page 42: ...n cause irreversible damage Type of alarm Code Type Restore ee Electric Automatic eE Electric From Auto to manual EE Electric Manual ii Idraulic Automatic iI Idraulic From Auto to manual II Idraulic M...

Page 43: ...ing ex days 2 4 5 6 3 select days 2 4 5 6 4 set event 1 event time state Off On Fan 5 set event 2 3 ecc 6 select days 1 3 7 7 set event 1 2 3 ecc The most recent schedule saved overrides the existing...

Page 44: ...other days of the week are automatically scheduled press Set event 1 example Tuesday 05 30 FAN press starts flashing set event time press set eventt minutes press iset desired mode 0 null 1 OFF 2 ECO...

Page 45: ...ON FAN 21 00 6 OFF OFF OFF OFF OFF OFF OFF Example day 5 change events 3 and 4 from ON to OFF set eventt minutes press iset desired mode 0 null 1 OFF 2 ECO 3 ON 4 Fan press Press to set other the even...

Page 46: ...46 press press 4 times event 4 press 3 times starts flashing 003 ON select mode 002 OFF confirm press 2 times to exit 003 15 00 5 16 3 C 17 00 002 15 00 5 003 15 00 5 002 15 00 5...

Page 47: ...ool COMMON OPERATIONS ON OFF ECO main menu cmd local status scegliere OFF ON ECO PUMP ON change MODE main menu cmd local mode select COOL HEAT change SETPOINT main menu unit parameters setpoint DISPLA...

Page 48: ...ts number dipend on unit s series The menu is repeated for each refrigerant circuit circuit circuit1 circuit2 thermostatic circuit1 circuit2 Setpoint Menu P0001 ManSet Manual temperature Setpoint P000...

Page 49: ...be enabled display actual value On pag xy unit parameters service maintenance P0500 1 Setting Select Confirm d01 Monday Scheduled day Active Time 1 xx yy Value 1 Eco Time 2 Value 2 Setting d01 Monday...

Page 50: ...Util Ok EE003 Guasto P1 Util Fault Press Press alarm log detail eE001 Monitore fase Fault 1 Critico A 14 02 2012 11 30 10 alarm list Reset Passive 1 eE001 Monitore fase Fault Select Confirm Select Co...

Page 51: ...t EE003 Guasto P1 Util Ok EE003 Guasto P1 Util Fault Alarm cnf AlarmSnapshot 0 Lista allarmi Ordinamento 1 Ora Ordinamento 2 Ora Ordine descrescente Passive Execute Allarmi cnf AlarmSnapshot 0 Lista a...

Page 52: ...g Circuit C1 Thermostatic C1 Unit option Thermoregulator Integrations Compressor Correction SH Sourse Ventilation Supply fan Defrost Humidity control Recovery renewal Reset usure Sensor settings Seria...

Page 53: ...5 1 board offline A ee046 Ambient pressure probe failure A ID Description Reset ee101 Circuit 1 module disconnection on Proces A ee102 Thermostatic valve driver timeout A ee104 Thermostatic valve bloc...

Page 54: ...Source frost M iI220 Source flow M II221 Source frost M fF109 DI Low Pressure A M ff110 Cool Low pressure Pre alarm A ff111 Low Heat Pressure pre alarm A fF112 AI Low Pressure A M fF113 DI High Press...

Page 55: ...RM 3001 Central POL687 IO Cmd Supply Fan_X5 AO 687 Modulating supply fan control percentage 3001 Central POL687 IO Cmd ExternalDamper_X7 AO 687 External damper opening control percentage 3001 Central...

Page 56: ...g 3003 Thermoregulator 16 Fch state Freecooling heating status 3003 Thermoregulator 17 Actual request for addition Reg requested for the additions 3003 Thermoregulator 18 Addition state Additions stat...

Page 57: ...p 2 status 0 Free 1 Active 2 Timed 3 Not enabled 3101 Circuit C1 Stata 1113 Comp 3 status 0 Free 1 Active 2 Timed 3 Not enabled 3101 Circuit C1 Stata 1114 Current cap Capacity currently employed on th...

Page 58: ...tact 3102 Circuit C1 IO Stata Ovl Source_DL2 DI 985 0 Fault 1 OK Status of the thermal protection contact of the source motors 3102 Circuit C1 IO Stata ElectFilter_X5 DI 985 0 Fault 1 OK Status of the...

Page 59: ...corrections 3201 Thermostatic C2 Stata 2201 AICalSuctSprHtP Current overheating value calculated 3201 Thermostatic C2 Stata 2202 ECVState 0 Idle 1 ECVAlarm 2 FailSafe 3 Referencing 4 Positioning 5 Po...

Page 60: ...status of the Lon device 4302 LonWorks 801 LonState Status of the Lon node 4302 LonWorks 802 LonBios Versione bios del modulo espansione LonWorks 3004 Expansion POL925 IO Input 1 X4 DIPOL687 ExFlow o...

Page 61: ...cked and equipped with the suitable warning sign make sure no tension is present After switching the power off wait at least 5 minutes before accessing to the electrical panel or any other electrical...

Page 62: ...power supply voltage vacuum and loaded X 16 absorption of the individual electric loads X 17 compressors carter heaters test X 18 leaks control 19 cooling circuit work parameters detection X 20 Safte...

Page 63: ...er jet machine Keep the direction parallel to the flow of the flaps to avoid damages Check the aluminium flaps have not been damaged or folded on the contrary contact an authorised after sales assista...

Page 64: ...d replacement of filters are very important from an hygienic sanitary point of view Operation with clogged filters leads to a reduction in the air flow rate with malfunctionings and block up to possib...

Page 65: ...me that keeps the filters lifted from the tank base to have a settling bottom for the muds Remove the pre filter by lifting it of about 1 cm and remove it as shown in figure 1 Position the filter to b...

Page 66: ...her wire stretching rod always by means of the curved beaks pliers Immerged electrodes humidifier Option Do not use solvents or detergents to clean the plastic components For descaling use a vinegar o...

Page 67: ...e mounting it the filter body does not require replacing wash it with water and remount it on the new cylinder using the new gasket provided with the latter check the seal gasket between the cylinder...

Page 68: ...area Professional electrical and electronic equipment must be disposed of by authorised personnel through established waste disposal authorities around the country In this regard here is the definiti...

Page 69: ...ly check the positioning of the unit The installation of the unit in a place unsuited to support its weight and or guarantee adequate anchorage may result in consequent damage to things people or the...

Page 70: ...t could be under voltage due to the start up of the unit may cause electric shocks burns and electrocution When voltage is necessary for the circuit open the isolator on the attachment line of the uni...

Page 71: ...5 48 6 55 4 64 8 69 9 79 2 COP 1 4 68 4 66 4 68 4 54 4 60 4 66 4 62 4 42 Heating capacity EN14511 2018 13 kW 149 8 158 7 185 4 208 9 235 1 285 3 302 8 326 8 COP EN14511 2018 13 3 53 3 43 3 43 3 37 3...

Page 72: ...99 95 98 88 84 75 70 67 72 92 54 4 101 95 95 90 87 78 74 72 72 92 60 4 105 95 95 91 86 80 75 73 72 93 70 4 106 96 95 92 88 83 77 75 73 94 80 4 106 97 96 93 89 82 77 75 74 95 90 4 107 101 100 94 92 85...

Page 73: ...orrect operating and maintenance of the unit operating at full load To verify the operation field of the operating units with percentages of outdoor air always calculate the Tm mixing temperature at t...

Page 74: ...sate drain 7 Functional spaces 8 Water heating coil inlet 1 1 2 9 Water heating coil outlet 1 1 2 10 Reheat coil optional 11 Treatment coil 12 water heating coil optional 13 F7 Electronic filters opti...

Page 75: ...Dimensional drawings 75...

Page 76: ...tal air supply AE Outdoor air intake CBK CCK CCKP version ES Exhaust air CCK CCKP version H1 Wall with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum c...

Page 77: ...Dimensional drawings 77...

Page 78: ...ply AE Outdoor air intake CBK CCK CCKP version ES Exhaust air CCK CCKP version H1 Wall with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WE...

Page 79: ...Dimensional drawings 79...

Page 80: ...ward air supply optional M5 Upflow air supply AE Outdoor air intake CBK CCK CCKP version ES Exhaust air CCK CCKP version H1 Wall with same height as unit on a maximum of three sides Anti vibration mou...

Page 81: ...Dimensional drawings 81...

Page 82: ...with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WEIGHT DISTRIBUTION SIZE 60 4 70 4 80 4 Configuration CAK CBK CCK CCKP CAK CBK CCK CCKP...

Page 83: ...Dimensional drawings 83...

Page 84: ...version H1 Wall with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WEIGHT DISTRIBUTION SIZE 60 4 70 4 80 4 Configuration CAK CBK CCK CCKP C...

Page 85: ...Dimensional drawings 85...

Page 86: ...air supply optional M5 Upflow air supply CBK CCK CCKP version AE Outdoor air intake ES Exhaust air CCK CCKP version H1 Wall with same height as unit on a maximum of three sides Anti vibration mount po...

Page 87: ...Dimensional drawings 87...

Page 88: ...with same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WEIGHT DISTRIBUTION SIZE 90 4 100 4 110 4 Configuration CAK CBK CCK CCKP CAK CBK CCK CCKP...

Page 89: ...Dimensional drawings 89...

Page 90: ...same height as unit on a maximum of three sides Anti vibration mount position Suggested minimum clearance WEIGHT DISTRIBUTION SIZE 90 4 100 4 110 4 Configuration CAK CBK CCK CCKP CAK CBK CCK CCKP CAK...

Page 91: ...Dimensional drawings 91...

Page 92: ...ra 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it FOR OVER 30 YEARS WE HAVE BEEN OFFERING SOLUTIONS TO ENSURE SUSTAINABLE COMFORT AND THE WELL BEING OF PEOPLE AND THE ENVIRON...

Reviews: