90
LEGEND FOR PAGES 85-90
Zone Set Points
R/W
htg_zat_sp_u
AV
203
The Zone Temperature Setpoint for unoccupied heating resides
in the Setpoint Microblock (Default is 60).
ZRH FAIL
R
zrh_failure
BV
853
The current ZRH Sensor Alarm status.
Z-RH From BAS
R/W
zrh_bas
AV
211
The current Zone Air Humidity (Z-RH) written to the controller by
the BAS system.
Z-RH Status
R
zrh_stat
AV
212
The current Zone Air Humidity (Z-RH) from the ZS sensor.
Table C — Mapping Points - Carrier 62X Rev. H - 100% Outdoor Air Air-to-Air (cont)
Display Name
Read/Write
BACnet
Description
Reference Name
Type
ID
OEM
—
Automated Logic Incorporated, a division of Carrier
APS
—
Air Pressure Switch
BAS
—
Building Automation System
CCS
—
Compressor Current Switch
CFI
—
Clogged Filter Indicator
CM1A
—
Compressor #1
CC1A
—
Compressor #1 Contactor Coil
CC1A-A1 —
Compressor #1 Auxiliary Contact
CFM
—
Cubic Feet per Minute (volumetric flow rate)
CPM
—
Compressor Protection Module
CM2A
—
Compressor #2
CC2A
—
Compressor #2 Contactor Coil
CC2A-A1 —
Compressor #2 Auxiliary Contact
DCM
—
Digital Compressor Module
DPT
—
Differential Pressure Transmitter
DOAU
—
Dedicated Outdoor Air Unit
DOM
—
Delay-On-Make
EC-RH
—
Entering Coil Relative Humidity, measured before
entering the DX coil and after the ERV
ECAT
—
Entering Coil Air Temperature, measured before
entering the DX coil and after the ERV
ERV
—
Energy Recovery Ventilator
EMR
—
Energy Management Relay; normally closed contact
EF
—
Exhaust Fan
EF-APS
—
Exhaust Fan Air Pressure Switch
EF-DPT
—
Differential Pressure Transmitter
EF-VFD
—
Exhaust Fan Variable Frequency Drive
FPM
—
Feet per Minutes (velocity)
FSC
—
Fan Speed Control
HAR
—
Heating Analog Relay
HARM
—
Heating Analog Relay Module
HGRH
—
Hot Gas Reheat
HPS
—
High Pressure Switch
HP1
—
High Pressure Switch #1
HP2
—
High Pressure Switch #2
LA
—
Low Ambient Pressure Sensor
LAT
—
Leaving Air Temperature
LP1
—
Low Pressure Switch #1
LP2
—
Low Pressure Switch #2
MDC
—
Modulating Discharge Controller
MDV
—
Modulating Discharge Valve
MRC
—
Modulating Reheat Controller
MRV
—
Modulating Reheat Valve
NC
—
Normally Closed contact
NO
—
Normally Opened contact
OA
—
Outside Air; prior to any conditioning
OD
—
Outside Air Damper
OA-RH
—
Outside Air Relative Humidity (real), measured
before air enters the ERV, if existing
OAT
—
Outside Air Temperature (real), measured before air
enters the ERV, if existing
OFM1
—
Outdoor Fan #1 Motor
OF1C
—
Outdoor Fan #1 Contactor Coil
OF1-
VFD
—
Outdoor Fan #1 Variable Frequency Drive
OFM2
—
Outdoor Fan #2 Motor
OF2C
—
Outdoor Fan #2 Contactor Coil
OF2-
VFD
—
Outdoor Fan #2 Variable Frequency Drive
RHR
—
Reheat Relay
RHS
—
Reheat Valve Solenoid
RTHO
—
Room Temperature Heating Override
RTRHO —
Room Temperature Reheat Override
SD
—
Smoke Detector; normally closed contact
SF
—
Supply Fan
SF-APS —
Supply Fan Air Pressure Switch
SF-DPT —
Differential Pressure Transmitter
SF-VFD —
Supply Fan Variable Frequency Drive
SLT
—
Suction Line Temperature, attached to the suction
line near the suction header of the DX coil
VFD
—
Variable Frequency Drive
WM
—
Wheel Motor
WMC
—
Wheel Motor Contactor
WM-VFD —
Wheel Motor Variable Frequency Drive
ZAT
—
Zone Air Temperature
Z-RH
—
Zone Relative Humidity