6. Slide the sampling tube collar over the sampling tube

until the tabs lock into the tube.

7. Slide sampling tube into smoke detector with eight slots.

Make sure sampling tube holes are aligned facing UP.

8. Insert plug into far end of the sampling tube.
9. Place rubber gaskets over each sampling tube on smoke

detector. (See Fig. 2.)

10. Remove one knockout from top of smoke detector.
11. Insert one end of RJ-45 wire harness through knockout

and wire to smoke detector as shown in Fig. 10.

12. Slide smoke detector into holes in fan side plate with

the terminal block at the top and secure using two,

8-18

3

/

4

-in. pan head screws (P/N AL56AU168). Replace

cover.

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage.
Do not overtighten the screws.

CAUTION

!

13. Attach cable to fan side plate using snap-in wire ties.

See Fig. 9 for clarification. Secure to center post.

14. Secure cable to back side of cable tray using three snap-in

wire ties.

15. In the Electrical/Compressor section, install snap bushing

in the center knockout underneath the terminal strips

lo-

cated in the bottom right-hand corner of control box.

16. Connect wires to terminal strips as shown in Fig. 6 for

Comfort

Link

t

units or Fig. 7 for Electro--Mechanical

Units.

NOTE

: This step is not needed with 48/50PG Humidi--MiZer

t

units because they have plug 19 harness already installed in the
control box. The harness assembly part number 50TG403507
that came with the accessory is not used. Factory installed PL--19
can be located outside the contol box by its appropriate label. For
Humidi--MiZer smoke detector wiring refer to Fig. 8.

17. Remove cover from control module and remove knockout

from side of module nearest the RJ-45 connector.

18. Using

three

8-18

3

/

4

-in.

pan

head

screws

(P/N AL56AU168) screws, secure control module to com-
pressor partition above compressor B1/A2 location.

19. Connect PL-19 from control module to PL-19 from wir-

ing harness installed in Step 16.

NOTE

: On 48PG Humidi--MiZer units, the control box harness

has a jumper plug attached. This needs to be disconnected so
PL--19 from the smoke detector can be snapped in.

20. Route cable from supply smoke sensor, along the outside

of the control box, through the control module knockout

and connect to the J1 RJ-45 connector.

21. Using wire ties, secure the wiring so it does not interfere

with unit operation.

22. Replace control module cover.
23. Restore power to the unit.
24. Configure

Comfort

Link controller as specified in Config-

uring the

Comfort

Link Controller below.

25. Perform Sensor and Controller tests. At a minimum, the

Magnet test should be performed to verify smoke detector
wiring.

26. Turn off power to the unit.
27. Reconnect the indoor fan plug and the limit switch wires if

applicable.

28. Close the indoor fan section door.
29. Restore power to the unit and check for alarms. Correct

any problems encountered.

30. Close Electrical/Compressor section door.

Sensor Installation (CRSMKSEN001A00)

When adding return smoke sensor to previously installed supply
smoke detector:

1. Open electrical/compressor section access door/panel.
2. Disconnect PL-19 from control module to terminal strip

by separating plug connectors.

3. Remove control module cover. Disconnect supply sensor

RJ-45 wire from control module.

4. Remove three screws attaching control module to com-

pressor partition and save screws for later use.

5. Remove control module from unit.
6. Slide feet of control module into receptacle on the return

sensor housing and secure from the backside using one

screw removed in Step 4. The J1 RJ-45 connector on sen-
sor should be nearest the control module. Knockout holes

should align. (See Fig. 11.)

7. Route short RJ-45 wire from J1 connector of sensor,

through knockout holes, and connect to J1 connector of
control module.

8. Follow steps 2-20 of instructions for installing return

smoke detector.

IMPORTANT

: Step 15 requires connecting the supply smoke

sensor RJ--45 wire to connector J2 in the control module.
When adding supply smoke sensor to previously installed return
smoke detector:
Follow steps 1-14 and 19-29 from supply smoke detector

installation instructions.

CR

S

M

K

Summary of Contents for 48/50HG014-028

Page 1: ...ric technology for the detection of smoke This detection method when combined with an efficient ducting design samples air passing through the unit If sufficient smoke is sensed an alarm signal is initiated and the ComfortLink controls will shut down the unit With the unit shut down the unit will not blow toxic smoke and fire gases throughout the areas served by the duct system The return air smok...

Page 2: ...UST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct WARNING INSTALLATION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage When installing the smoke detector in the unit follow all local codes CAUTION C...

Page 3: ...ke detector prior to making duct connections 1 Open the hinged electrical compressor access door and secure 2 Find the 2 plugs located above compressor B1 A2 remove and discard Cut holes in the insulation located be hind the partition 3 Remove cover from smoke detector The screws will remain captured in the cover 4 Slide exhaust tube into the sensor The exhaust tube should be inserted from the bac...

Page 4: ...50PG Humidi MiZert units because they have plug 19 harness already installed in the control box The harness assembly part number 50TG403507 that came with the accessory is not used Factory installed PL 19 can be located outside the contol box by its appropriate label For Humidi MiZer smoke detector wiring refer to Fig 8 16 Connect PL 19 from the smoke detector control module to the PL 19 on the co...

Page 5: ...to installation of this accessory make sure all power is disconnected to the unit and locked out and tagged WARNING 1 Open the indoor fan access door and secure 2 Open and secure hinged electrical compressor access door 3 Disconnect wires located on the right hand side of the fan deck On gas heat units the indoor fan plug and the limit switch quick connects must be disconnected On units without ga...

Page 6: ...6 C07178 Fig 7 Smoke Detector Wiring on Electro Mechanical Control Units C07179 Fig 8 48 50PG Humidi MiZert Smoke Detector Wiring CRSMK ...

Page 7: ...On 48PG Humidi MiZer units the control box harness has a jumper plug attached This needs to be disconnected so PL 19 from the smoke detector can be snapped in 20 Route cable from supply smoke sensor along the outside of the control box through the control module knockout and connect to the J1 RJ 45 connector 21 Using wire ties secure the wiring so it does not interfere with unit operation 22 Repla...

Page 8: ...d in the unit Default password is 1111 Use the arrow keys to scroll the red LED on the display to the Configuration position and press ENTER Scroll through the menu until UNIT is found and press ENTER After reaching the UNIT sub menu scroll to FS SW Fire Shutdown Input and press ENTER twice change the value to 1 Normal Open with the arrow keys press ENTER again Press ESCAPE three times to return t...

Page 9: ...after S Perform a sensor alarm test on each sensor connected to the controller upon installation and once every 12 months thereafter S Perform a sensor dirty test upon installation and once every 6 months thereafter or more frequently as conditions warrant Sensor Tests Sensor Alarm Test The sensor alarm test checks a sensor s ability to signal an alarm state This test requires the use of a SD MAG ...

Page 10: ...nd JP3 are set correctly on the controller before applying power 2 Verify that power is applied to the controller s supply in put terminals If power is not present replace or repair wir ing as required Trouble LED Controller s Trouble LED is On 1 Check the Trouble LED on each sensor connected to the controller If a sensor s Trouble LED is on determine the cause and make the necessary repairs 2 Che...

Reviews: