10. Mount the sampling tube support bracket to the

cross member with two 1/4AB-14 5/8-in. screws

(P/N AL48AM307) as shown in Fig. 5. Insert large snap
bushing (P/N HY93NH085) into hole in bracket.

11. Slide sampling tube into bracket. (See Fig. 4.) Pull the

sampling tube so that the locking collar snaps into the
smoke detector.

12. Attach smoke detector to partition using two, 8-18 3/4-in.

pan head screws (P/N AL56AU168).

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage.
Do not overtighten the screws.

CAUTION

!

13. Replace the unit side panel.
14. Install the snap bushing (P/N HY93NH069) in the center

knockout underneath the control terminal strips located in
the bottom right-hand corner of the control box.

15. Feed wires through snap bushing and connect to appropri-

ate terminals as shown in Fig. 6 for

Comfort

Link

t

units

or Fig. 7 for Electro--Mechanical units.

NOTE

: This step is not needed with 48/50PG Humidi--MiZer

t

units because they have plug 19 harness already installed in the
control box. The harness assembly part number 50TG403507
that came with the accessory is not used. Factory installed PL--19
can be located outside the contol box by its appropriate label. For
Humidi--MiZer smoke detector wiring refer to Fig. 8.

16. Connect PL-19 from the smoke detector control module to

the PL-19 on the control box harness installed in Step 15.

NOTE

: On 48PG Humidi--MiZer units the control box harness

has a jumper plug attached. This needs to be disconnected so
PL--19 from the smoke detector can be snaped in.

17. Restore power to the unit.
18. Configure

Comfort

Link controller as specified in

Con-

figuring the

Comfort

Link Controller.

19. Perform Sensor and Controller tests. At a minimum, the

Magnet test should be performed to verify smoke detector

wiring.

20. Replace smoke detector cover.
21. Check for alarms. Correct any problems.

INSTALL SUPPLY SENSOR TUBE

WITH HOLES POINTING

UP

INSTALL RETURN SENSOR TUBE

WITH HOLES POINTING

DOWN

BUSHING

BRACKET

INSTALL RETURN EXHAUST
TUBE HERE

C07175

Fig. 4

---

Supply and Return Sensor Tube

CR

S

M

K

Summary of Contents for 48/50HG014-028

Page 1: ...ric technology for the detection of smoke This detection method when combined with an efficient ducting design samples air passing through the unit If sufficient smoke is sensed an alarm signal is initiated and the ComfortLink controls will shut down the unit With the unit shut down the unit will not blow toxic smoke and fire gases throughout the areas served by the duct system The return air smok...

Page 2: ...UST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct WARNING INSTALLATION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage When installing the smoke detector in the unit follow all local codes CAUTION C...

Page 3: ...ke detector prior to making duct connections 1 Open the hinged electrical compressor access door and secure 2 Find the 2 plugs located above compressor B1 A2 remove and discard Cut holes in the insulation located be hind the partition 3 Remove cover from smoke detector The screws will remain captured in the cover 4 Slide exhaust tube into the sensor The exhaust tube should be inserted from the bac...

Page 4: ...50PG Humidi MiZert units because they have plug 19 harness already installed in the control box The harness assembly part number 50TG403507 that came with the accessory is not used Factory installed PL 19 can be located outside the contol box by its appropriate label For Humidi MiZer smoke detector wiring refer to Fig 8 16 Connect PL 19 from the smoke detector control module to the PL 19 on the co...

Page 5: ...to installation of this accessory make sure all power is disconnected to the unit and locked out and tagged WARNING 1 Open the indoor fan access door and secure 2 Open and secure hinged electrical compressor access door 3 Disconnect wires located on the right hand side of the fan deck On gas heat units the indoor fan plug and the limit switch quick connects must be disconnected On units without ga...

Page 6: ...6 C07178 Fig 7 Smoke Detector Wiring on Electro Mechanical Control Units C07179 Fig 8 48 50PG Humidi MiZert Smoke Detector Wiring CRSMK ...

Page 7: ...On 48PG Humidi MiZer units the control box harness has a jumper plug attached This needs to be disconnected so PL 19 from the smoke detector can be snapped in 20 Route cable from supply smoke sensor along the outside of the control box through the control module knockout and connect to the J1 RJ 45 connector 21 Using wire ties secure the wiring so it does not interfere with unit operation 22 Repla...

Page 8: ...d in the unit Default password is 1111 Use the arrow keys to scroll the red LED on the display to the Configuration position and press ENTER Scroll through the menu until UNIT is found and press ENTER After reaching the UNIT sub menu scroll to FS SW Fire Shutdown Input and press ENTER twice change the value to 1 Normal Open with the arrow keys press ENTER again Press ESCAPE three times to return t...

Page 9: ...after S Perform a sensor alarm test on each sensor connected to the controller upon installation and once every 12 months thereafter S Perform a sensor dirty test upon installation and once every 6 months thereafter or more frequently as conditions warrant Sensor Tests Sensor Alarm Test The sensor alarm test checks a sensor s ability to signal an alarm state This test requires the use of a SD MAG ...

Page 10: ...nd JP3 are set correctly on the controller before applying power 2 Verify that power is applied to the controller s supply in put terminals If power is not present replace or repair wir ing as required Trouble LED Controller s Trouble LED is On 1 Check the Trouble LED on each sensor connected to the controller If a sensor s Trouble LED is on determine the cause and make the necessary repairs 2 Che...

Reviews: