background image

9

The smoke detector contains a photoelectric detector approved
for an extended air speed range of

100 to 4000 feet per minute

and an operational temperature range of -4

_

to 158

_

F. Do not

operate the smoke detector out of these ranges.
The smoke detector operates on 24 vac, 120 vac, or

220/240 vac. The thermostat power terminals on the unit are used
to power the smoke detector.
The cover of the controller contains the Alarm, Trouble, Dirty
and Power LEDs. The cover of the sensor contains the Alarm,

Trouble and Power LEDs. (See Fig 2.)
The smoke detector can be reset by a momentary power
interruption, by the reset button on the front cover, by the control

panel, or by the remote reset accessory.

RETURN SENSOR

CONTROL MODULE

SECURE FROM BEHIND

WITH SCREW

J1

S

E

J1

J2

S

E

RETURN SENSOR

J1

J2

CONTROL MODULE

J1

TERMINAL STRIP

C07182

Fig. 11

---

Sensor Installation

Airflow

HVAC duct

Sampling

tube

Retainer
clip

Optic
plate

Optic
housing

Sensor 
housing

C07183

Fig. 12

---

Sensor Cleaning Diagram

MAINTENANCE

IMPORTANT

: Notify the proper authorities that the smoke

detector system is undergoing maintenance, and that the system
will temporarily be out of service. Disable the zone or system
undergoing maintenance to prevent unwanted alarms and
possible dispatch of the fire department.

Cleaning Procedure

1. Disconnect power from the duct detector then remove the

sensor’s cover.

2. Using a vacuum cleaner, clean compressed air, or a soft

bristle brush, remove loose dirt and debris from inside the
sensor housing and cover. (See Fig 12.)

Use isopropyl alcohol and a lint-free cloth to remove dirt
and other contaminants from the gasket on the sensor’s
cover.

3. Squeeze the retainer clips on both sides of the optic hous-

ing then lift the housing away from the printed circuit

board.

4. Gently remove dirt and debris from around the optic plate

and inside the optic housing.

5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a sensor

alarm test.

Recommended Service Schedule

S

Visually inspect each sensor connected to the controller
upon installation and once every 6 months thereafter.

S

Perform a sensor alarm test on each sensor connected

to the controller upon installation and once every
12 months thereafter.

S

Perform a sensor dirty test upon installation and once
every 6 months thereafter or more frequently, as
conditions warrant.

Sensor Tests

Sensor Alarm Test

The sensor alarm test checks a sensor’s ability to signal an alarm
state. This test requires the use of a SD-MAG test magnet.

IMPORTANT

: This test places the duct detector into the alarm

state. Unless part of the test, disconnect all auxiliary equipment
from the controller before performing the test. If duct detector is
connected to a fire alarm system, notify the proper authorities
before performing the test.
To perform a sensor alarm test:

1. Hold the test magnet where indicated on the side of the

sensor housing for seven seconds. Verify that the sensor’s
Alarm LED turns on.

2. Reset the sensor by holding the test magnet against the

sensor housing for two seconds. Verify that the sensor’s
Alarm LED turns off.

Sensor Dirty Test

The sensor dirty test provides an indication of the sensor’s ability

to compensate for gradual environmental changes. A sensor that
can no longer compensate for environmental changes is

considered 100% dirty and requires cleaning or replacing. This
test requires the use of a SD-MAG test magnet.
To perform a sensor dirty test, hold the test magnet where

indicated on the side of the sensor housing for seven seconds.
Verify that the sensor’s Dirty LED flashes.

IMPORTANT

: Holding the test magnet against the sensor

housing for longer than 7 seconds will put the duct detector into
the alarm state and activate all automatic alarm responses.
The sensor’s Dirty LED indicates the results of the dirty test as
shown below.

FLASHES

DESCRIPTION

1

0 to 25% dirty. This is typical on a newly installed duct

detector.

2

26 to 50% dirty

3

51 to 75% dirty

4

76 to 99% dirty

Controller Tests

Controller Alarm Test

The controller alarm test checks the controller’s ability to initiate
and indicate an alarm state

.

IMPORTANT

: This test places the duct detector into the alarm

state. Unless part of the test, disconnect all auxiliary equipment
from the controller before performing the test. If duct detector is
connected to a fire alarm system, notify the proper authorities
before performing the test.

CR

S

M

K

Summary of Contents for 48/50HG014-028

Page 1: ...ric technology for the detection of smoke This detection method when combined with an efficient ducting design samples air passing through the unit If sufficient smoke is sensed an alarm signal is initiated and the ComfortLink controls will shut down the unit With the unit shut down the unit will not blow toxic smoke and fire gases throughout the areas served by the duct system The return air smok...

Page 2: ...UST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct WARNING INSTALLATION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage When installing the smoke detector in the unit follow all local codes CAUTION C...

Page 3: ...ke detector prior to making duct connections 1 Open the hinged electrical compressor access door and secure 2 Find the 2 plugs located above compressor B1 A2 remove and discard Cut holes in the insulation located be hind the partition 3 Remove cover from smoke detector The screws will remain captured in the cover 4 Slide exhaust tube into the sensor The exhaust tube should be inserted from the bac...

Page 4: ...50PG Humidi MiZert units because they have plug 19 harness already installed in the control box The harness assembly part number 50TG403507 that came with the accessory is not used Factory installed PL 19 can be located outside the contol box by its appropriate label For Humidi MiZer smoke detector wiring refer to Fig 8 16 Connect PL 19 from the smoke detector control module to the PL 19 on the co...

Page 5: ...to installation of this accessory make sure all power is disconnected to the unit and locked out and tagged WARNING 1 Open the indoor fan access door and secure 2 Open and secure hinged electrical compressor access door 3 Disconnect wires located on the right hand side of the fan deck On gas heat units the indoor fan plug and the limit switch quick connects must be disconnected On units without ga...

Page 6: ...6 C07178 Fig 7 Smoke Detector Wiring on Electro Mechanical Control Units C07179 Fig 8 48 50PG Humidi MiZert Smoke Detector Wiring CRSMK ...

Page 7: ...On 48PG Humidi MiZer units the control box harness has a jumper plug attached This needs to be disconnected so PL 19 from the smoke detector can be snapped in 20 Route cable from supply smoke sensor along the outside of the control box through the control module knockout and connect to the J1 RJ 45 connector 21 Using wire ties secure the wiring so it does not interfere with unit operation 22 Repla...

Page 8: ...d in the unit Default password is 1111 Use the arrow keys to scroll the red LED on the display to the Configuration position and press ENTER Scroll through the menu until UNIT is found and press ENTER After reaching the UNIT sub menu scroll to FS SW Fire Shutdown Input and press ENTER twice change the value to 1 Normal Open with the arrow keys press ENTER again Press ESCAPE three times to return t...

Page 9: ...after S Perform a sensor alarm test on each sensor connected to the controller upon installation and once every 12 months thereafter S Perform a sensor dirty test upon installation and once every 6 months thereafter or more frequently as conditions warrant Sensor Tests Sensor Alarm Test The sensor alarm test checks a sensor s ability to signal an alarm state This test requires the use of a SD MAG ...

Page 10: ...nd JP3 are set correctly on the controller before applying power 2 Verify that power is applied to the controller s supply in put terminals If power is not present replace or repair wir ing as required Trouble LED Controller s Trouble LED is On 1 Check the Trouble LED on each sensor connected to the controller If a sensor s Trouble LED is on determine the cause and make the necessary repairs 2 Che...

Reviews: