To perform a controller alarm test:

1. Press the controller’s test/reset switch for seven seconds.

Verify that the controller’s Alarm LED turns on.

2. After performing a controller alarm test, reset the sensor

by pressing the test/reset switch for two seconds. Verify
that the controller’s Alarm LED turns off.

Controller Dirty Test

The controller dirty test checks the controller’s ability to initiate a

sensor dirty test and indicate its results.
To perform a sensor dirty test, press the controller’s test/reset
switch for two seconds. Verify that the controller’s Trouble LED

flashes.

TROUBLESHOOTING

Dirty LED

Sensor’s Dirty LED is Flashing

Clean the sensor assembly as described in Cleaning Procedure.

Power LED

Sensor’s Power LED is OFF

1. Check the controller’s Power LED. If it is off, determine

why the controller does not have power and make the

necessary repairs.

2. Check the wiring between the sensor and the controller. If

wiring is loose or missing, repair or replace as required.

Controller’s Power LED is OFF

1. Make sure the circuit supplying power to the controller is

operational. If not, make sure JP2 and JP3 are set correctly
on the controller before applying power.

2. Verify that power is applied to the controller’s supply in-

put terminals. If power is not present, replace or repair wir-

ing as required.

Trouble LED

Controller’s Trouble LED is On

1. Check the Trouble LED on each sensor connected to the

controller. If a sensor’s Trouble LED is on, determine the
cause and make the necessary repairs.

2. Check the wiring between the sensor and the controller. If

wiring is loose or missing, repair or replace as required.

Controller’s Trouble LED is Flashing

1. One or both of the sensors is 100% dirty. Determine which

sensor’s Dirty LED is flashing.

2. Clean the sensor assembly as described in Cleaning

Procedure.

Sensor’s Trouble LED is On

1. Check the sensor’s Dirty LED. If it is flashing, the sensor

is dirty and must be cleaned.

2. Check the sensor’s cover. If it is loose or missing, secure

the cover to the sensor housing.

3. Replace sensor assembly.

Sensor’s Trouble LED is On But Controller’s Trouble LED is
Off

Remove JP1 on the controller.

Copyright 2007 Carrier Corp.

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No:48/50H,P---24SI

Replaces:48/50H,P--- 10SI

Printed in U.S.A.

Edition Date:7/07

CR

S

M

K

Summary of Contents for 48/50HG014-028

Page 1: ...ric technology for the detection of smoke This detection method when combined with an efficient ducting design samples air passing through the unit If sufficient smoke is sensed an alarm signal is initiated and the ComfortLink controls will shut down the unit With the unit shut down the unit will not blow toxic smoke and fire gases throughout the areas served by the duct system The return air smok...

Page 2: ...UST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct WARNING INSTALLATION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage When installing the smoke detector in the unit follow all local codes CAUTION C...

Page 3: ...ke detector prior to making duct connections 1 Open the hinged electrical compressor access door and secure 2 Find the 2 plugs located above compressor B1 A2 remove and discard Cut holes in the insulation located be hind the partition 3 Remove cover from smoke detector The screws will remain captured in the cover 4 Slide exhaust tube into the sensor The exhaust tube should be inserted from the bac...

Page 4: ...50PG Humidi MiZert units because they have plug 19 harness already installed in the control box The harness assembly part number 50TG403507 that came with the accessory is not used Factory installed PL 19 can be located outside the contol box by its appropriate label For Humidi MiZer smoke detector wiring refer to Fig 8 16 Connect PL 19 from the smoke detector control module to the PL 19 on the co...

Page 5: ...to installation of this accessory make sure all power is disconnected to the unit and locked out and tagged WARNING 1 Open the indoor fan access door and secure 2 Open and secure hinged electrical compressor access door 3 Disconnect wires located on the right hand side of the fan deck On gas heat units the indoor fan plug and the limit switch quick connects must be disconnected On units without ga...

Page 6: ...6 C07178 Fig 7 Smoke Detector Wiring on Electro Mechanical Control Units C07179 Fig 8 48 50PG Humidi MiZert Smoke Detector Wiring CRSMK ...

Page 7: ...On 48PG Humidi MiZer units the control box harness has a jumper plug attached This needs to be disconnected so PL 19 from the smoke detector can be snapped in 20 Route cable from supply smoke sensor along the outside of the control box through the control module knockout and connect to the J1 RJ 45 connector 21 Using wire ties secure the wiring so it does not interfere with unit operation 22 Repla...

Page 8: ...d in the unit Default password is 1111 Use the arrow keys to scroll the red LED on the display to the Configuration position and press ENTER Scroll through the menu until UNIT is found and press ENTER After reaching the UNIT sub menu scroll to FS SW Fire Shutdown Input and press ENTER twice change the value to 1 Normal Open with the arrow keys press ENTER again Press ESCAPE three times to return t...

Page 9: ...after S Perform a sensor alarm test on each sensor connected to the controller upon installation and once every 12 months thereafter S Perform a sensor dirty test upon installation and once every 6 months thereafter or more frequently as conditions warrant Sensor Tests Sensor Alarm Test The sensor alarm test checks a sensor s ability to signal an alarm state This test requires the use of a SD MAG ...

Page 10: ...nd JP3 are set correctly on the controller before applying power 2 Verify that power is applied to the controller s supply in put terminals If power is not present replace or repair wir ing as required Trouble LED Controller s Trouble LED is On 1 Check the Trouble LED on each sensor connected to the controller If a sensor s Trouble LED is on determine the cause and make the necessary repairs 2 Che...