30312267 

     

                                                                                           

                         

  Issue 1.08

 

                                       

 

Features

 

 

Integrated  algorithm  of  analyzing  fire,  recognize  black  smoke 
quickly. 

 

Drift sensitivity, suit to environment extensively. 

 

Removable innovative sensing chamber, easy for maintenance.   

 

The fire LED allows 360

°

viewing. 

 

Providing remote terminals connect with remote indicator. 

 

Featuring magnetic test. 

 

2-level sensitivities (complying with EN 54-7 just when sensitivity is 
level 1).

 

Description

 

DC-9102E 

Conventional 

Photoelectric 

Smoke 

Detector 

is 

new-generation  product.  With  built-in  microprocessor,  the  detector  is 
highly  fixed  with  reliable  fire  judging  program,  which  make  it  stable  and 
reliable performance. 

When  the  detector  checks  fire  signal,  it  will  send  fire  information  to  the 
control  panel  or  addressable  zone  monitor  unit  by  means  of  current 
changing. The detector keeps turning  on the LED to indicate  alarm state 
until it is reset. 

The detector is developed from sensing chamber by scattering theory. It 
has the ability to resist dust contamination and environmental light.

 

The detector utilizes drift compensation algorithm: When the environment 
is  changing,  such  as  dust  accumulation,  humidity  and  temperature 
changing, the detector can  figure  out these  drift variation to make up  for 
sensitivity,  thus  the  amount  of  smoke  needed  to  generate  an  alarm 
remains constant, irrespective  of  environmental conditions. The principle 
diagram is shown as Fig. 1.

 

     

Smoke density                                        Smoke density

 

 

 

 

 

a  Fixed  sensitivity                      b  Environment  value  after  drifting  (prone 

to nuisance alarm) 

c Normal environment value      A Variable sensitivity

 

Fig. 1

 

Connection and cabling

 

The orientation base is shown in Fig. 3.

 

C

B

A

 

Fig. 2                                    Fig. 3

 

There  are  four  terminals  with  number  on  the  base. 

“1”  is  connected  with 

output  anode  of addressable zone monitor unit  or the  anode  of the power 
supply; 

“2”  is  used  as  output,  connected  with  anode  of  next  detector 

(Terminal  1)  and  also  connected  with  anode  of  remote  indicator; 

“3”  is 

connected  with  output  cathode  of  addressable  zone  monitor  unit  or  the 
cathode  of  the  power  supply  as  well  as  the  cathode  of  next  detector; 

“4” 

connects with the cathode of remote indicator. 

Recommended Wiring 

1.0mm

or  above  fire  cable  for  all  terminals  laid  through  metal  conduit  or 

flame proof conduit, subject to local codes. 

Note: Different color cables are used to avoid wiring mistake.

 

 

Installation

 

Fix the base with two taping screws. Then align A (Fig.2) on the bottom of 
the detector to B (Fig.3) of the base, and rotate the detector clockwise to 
mark C.

 

Mounting of the detector is shown in Fig.4.

 

Electrical Box

Conduit

Detector

51.5mm

Orientation Base

 

Fig. 4 

Application

 

Notes: The alarm current depends on the current limit of the control 
panel.  24VDC  cannot  power  the  detector  directly.  Otherwise  the 
detector will be blown up for lack of current limit resistor.

 

The  sensitivity  level  1  and  polling  LED  status  is

 

“ON”  are default, which 

can be modified by P-9910B programmer.   

Program  parameters:  In  power-on  state,  input  unlocking  password  and 
press 

Clear

 to unlock. Press 

Function

, then press “3”, the screen shows 

“-” at the last digit. Input corresponding sensitivity or parameter and press 

Program

,  the  screen  will  show  a  “P”,  the  corresponding  sensitivity  or 

parameter  is  programmed.  Press 

Clear

  to  clear  the  "P".  Input  locking 

password and press 

Clear

 to return. 

Table 1 Parameters Setup 

Parameter   

Smoke 
Sensitivity 

Polling LED 

Status 

ON 

ON 

129 

OFF 

130 

OFF 

Read  sensitivity:  On  power-on  time,  press 

Test

,  the  LCD  screen  shows 

the  address  of  the  detector;  Press 

Up

,  it  shows  in  turn  the  sensitivity, 

device type, initial sensitivity. 

The detector is  suitable for hotels,  restaurants,  office  buildings, teaching 
buildings,  banks,  warehouses,  libraries,  computer  rooms  and  switch 
rooms, etc.

 

 

When  the  detector  connects  with  conventional  fire  alarm  control 

panel or addressable zone monitor unit from GST, and if DP-9907 Active 
End  of  Line  Unit  is  connected  to  the  end  of  output  loop,  DB-01D  base 
should be used.

 

 

Used  as  the  detector  base,  DP-9907  Active  End  of  Line  is 

used  to  be  installed  a  conventional  detector  on  it.  The  system 
connection is shown in Fig. 5.

 

O

-

O

+

 

Fig. 5 

DC-9102E   

Conventional Photoelectric 

Smoke Detector 

Time 

Time 

548d/03 

2831-CPR-F0003 

GST-0007-01 

    14 

 