2

Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.

DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies a hazard

which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to

highlight suggestions which

will

result in enhanced installation,

reliability, or operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personal

injury, death and/or equipment damage.
Disconnect all power to the unit before performing

maintenance or service.

Install Lock Out tags on

disconnects or breakers.

!

WARNING

FIRE HAZARD

Failure to follow this warning could cause personal

injury and/or death.
The National Fire Protection

Association has

established that DUCT DETECTORS MUST NOT BE

USED AS A SUBSTITUTE FOR OPEN AREA

DETECTOR PROTECTION as a means of providing

life safety. Nor are they a substitute for early warning in

a building’s regular fire detection system. Carrier

supports this position and strongly recommends that the

user read NFPA Standards 90A, 72, and 101. This

smoke detector is listed per UL 268A.

!

WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could cause personal

injury.
This device will not operate without electrical power.

Fire situations may cause an interruption of power. The

system safeguards should be discussed with your local

fire protection specialist.

!

WARNING

FIRE HAZARD

Failure to follow this warning could cause personal

injury and/or equipment damage.
This device will not sense smoke unless the ventilation

system is operating and the cover is installed.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personal

injury and/or equipment damage.
For this detector to function properly, it MUST be

installed according to the instructions in this manual.

The detector MUST be operated within ALL electrical

and environmental specifications listed in this manual.

Failure to comply with these requirements may prevent

the detector from activating when smoke is present in

the air duct.

!

WARNING

INSTALLATION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage.
When installing the smoke detector in the unit, follow all

local codes.

CAUTION

!

Check Package Contents

Remove accessory packaging and inspect shipment for damage.
If any damage is found, file a claim with the shipping agent

immediately. If any item is missing or any part does not assemble

properly, notify the Carrier distributor.
Table 1 lists the accessory package contents. Fig. 2 shows the

smoke detector.

Return Air Smoke Detector Installation

(CRSMKDET001D00)

The return air smoke detector is to be installed in the predrilled

holes

located

above

compressor

B1/A2

in

the

electrical/compressor section. (See Fig. 3.)

Table 1—Accessory Package Contents — Return Air Smoke Detector (CRSMKDET001D00),

Supply Air Smoke Detector (CRSMKSUP001B00), Sensor (CRSMKSEN001A00)

UNIT

RETURN SMOKE DETECTOR

CRSMKDET001D00

SUPPLY SMOKE DETECTOR

CRSMKSUP001B00

ADDITIONAL SENSOR

CRSMKSEN001A00

Description

Part Number Quantity

Description

Part Number Quantity

Description

Part Number Quantity

48/50HG014-028,

48/50PG20-28

Sensor/Controller/

Harness/Tube

HK61ZT001

1

Controller/

RJ-45 Harness

HK28ZT001

1

Sensor Module

HK50ZT001

1

Screw

AL56AU168

2

Screw

AL56AU168

5

Screw

AL56AU168

1

Screw

AL48AM397

2

Sensor Module

HK50ZT001

1

Screw

AL48AM397

2

Bracket

50TG501113

1

Tube

RN20ZT008

1

Bracket

50TG501113

1

Large Bushing

HY93NH085

1

Cable Assy

RM91ZT015

1

Large Bushing

HY93NH085

1

Sampling Tube

RN20ZT060

1

Plug

1

Sampling Tube

RN20ZT060

1

Plug

1

Rubber Gasket

2

Plug

1

Rubber Gasket

2

Sampling Tube Collar

1

Rubber Gasket

2

Sampling Tube Collar

1

Snap-in Wire Tie

HY76TB110

2

Sampling Tube Collar

1

Wire Tie

HY76TB125

1

Wire Tie

HY76TB125

2

Tube

RN20ZT008

1

Bushing

HY93NH069

1

Bushing

HY93NH069

1

Cable Assy

RM91ZT015

1

Harness Assy

50TG403507

1

Harness Assy

50TG403507

1

Snap-in Wire Tie

HY76TB110

5

Exhaust Tube

1

Exhaust Tube

1

Wire Tie

HY76TB125

1

Cable Assy

RM91ZT001

1

Exhaust Tube

1

CR

S

M

K

Summary of Contents for 48/50HG014-028

Page 1: ...ric technology for the detection of smoke This detection method when combined with an efficient ducting design samples air passing through the unit If sufficient smoke is sensed an alarm signal is initiated and the ComfortLink controls will shut down the unit With the unit shut down the unit will not blow toxic smoke and fire gases throughout the areas served by the duct system The return air smok...

Page 2: ...UST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct WARNING INSTALLATION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage When installing the smoke detector in the unit follow all local codes CAUTION C...

Page 3: ...ke detector prior to making duct connections 1 Open the hinged electrical compressor access door and secure 2 Find the 2 plugs located above compressor B1 A2 remove and discard Cut holes in the insulation located be hind the partition 3 Remove cover from smoke detector The screws will remain captured in the cover 4 Slide exhaust tube into the sensor The exhaust tube should be inserted from the bac...

Page 4: ...50PG Humidi MiZert units because they have plug 19 harness already installed in the control box The harness assembly part number 50TG403507 that came with the accessory is not used Factory installed PL 19 can be located outside the contol box by its appropriate label For Humidi MiZer smoke detector wiring refer to Fig 8 16 Connect PL 19 from the smoke detector control module to the PL 19 on the co...

Page 5: ...to installation of this accessory make sure all power is disconnected to the unit and locked out and tagged WARNING 1 Open the indoor fan access door and secure 2 Open and secure hinged electrical compressor access door 3 Disconnect wires located on the right hand side of the fan deck On gas heat units the indoor fan plug and the limit switch quick connects must be disconnected On units without ga...

Page 6: ...6 C07178 Fig 7 Smoke Detector Wiring on Electro Mechanical Control Units C07179 Fig 8 48 50PG Humidi MiZert Smoke Detector Wiring CRSMK ...

Page 7: ...On 48PG Humidi MiZer units the control box harness has a jumper plug attached This needs to be disconnected so PL 19 from the smoke detector can be snapped in 20 Route cable from supply smoke sensor along the outside of the control box through the control module knockout and connect to the J1 RJ 45 connector 21 Using wire ties secure the wiring so it does not interfere with unit operation 22 Repla...

Page 8: ...d in the unit Default password is 1111 Use the arrow keys to scroll the red LED on the display to the Configuration position and press ENTER Scroll through the menu until UNIT is found and press ENTER After reaching the UNIT sub menu scroll to FS SW Fire Shutdown Input and press ENTER twice change the value to 1 Normal Open with the arrow keys press ENTER again Press ESCAPE three times to return t...

Page 9: ...after S Perform a sensor alarm test on each sensor connected to the controller upon installation and once every 12 months thereafter S Perform a sensor dirty test upon installation and once every 6 months thereafter or more frequently as conditions warrant Sensor Tests Sensor Alarm Test The sensor alarm test checks a sensor s ability to signal an alarm state This test requires the use of a SD MAG ...

Page 10: ...nd JP3 are set correctly on the controller before applying power 2 Verify that power is applied to the controller s supply in put terminals If power is not present replace or repair wir ing as required Trouble LED Controller s Trouble LED is On 1 Check the Trouble LED on each sensor connected to the controller If a sensor s Trouble LED is on determine the cause and make the necessary repairs 2 Che...