Fire alarm systems 

Enclosed 

addressable manual 

call point  

3339 

 

Attractive design compliant with EN54-11.  IP rating IP56 

 

Test key for routine testing without breaking the glass element 

 

Protection against accidental operation 

General 

The  call  point  has  an  attractive  design 
compliant  with  EN54-11,  and  is  surface 
mounted in the supplied red back box.  It has 
a clip retained front cover that makes it easy 
to  replace  the  glass  element  and  adds 
security  since  the  clips  are  concealed.    The 
frangible  element  is  a  glass  element  with  a 
protective  plastic  film.    To  operate  the  call 
point, the glass element is pressed until it is 
broken.  This will activate the built-in micro 
switch,  which  will  generate  a  fire  alarm  in 
the c.i.e.   

Test / cover removal key 

Routine testing is made with a supplied test 
key,  without  breaking  the  glass  element.  
Inserting the test key simulates the breaking 
of the glass element.  The call point  will be 
reset  when  the  test  key  is  pulled  out.    The 
test  key  is  also  used  to  release  the  security 
clips for the front cover removal. 

Protective cover 

To  protect  the  call  point  against  accidental 
operation,  a  transparent  polycarbonate  flap 
has  to  be  lifted  to  get  access  to  the  glass 
element. 

Encapsulated circuit 

All  electronics  are  encapsulated.    Only  the 
terminal  block  is  accessible  from  the  rear.  
Mounted  in  the  supplied  red  back  box  with 
the  tightening  gasket  on  place  (see  the 
opposite page), the IP rating is IP56. 

LED indicator 

An LED on the front cover indicates fire  

alarm generated by the call point.   
Furthermore it can via Win512 / Win128 be 
set to be flashing or non-flashing: 

Flashing LED

:  Is indicating that the c.i.e. is 

communicating  with  the  call  point.    When 
the  call  point  is  operated  the  LED  will  be 
turned on continuously. 

Non-flashing LED

:  The LED is turned off 

until the  call  point is  operated  and  the  LED 
will be turned on continuously. 

Connections / Settings 

The  COM  loop  is  connected  directly  to  the 
call  point  via  a  4-way  terminal  block.    For 
COM  loop  address  setting  is  the  address 
setting tool 3314 used.  3314 is also used to 
set the call point type and the LED mode: 

 

NORMAL

  mode:    (EBL512  SW 

version  >2.0  /  EBL128).    M.c.p.  type 
3339.  (Flashing  or  non-flashing  LED  is 
set via Win512 / Win128.) 

 

2330

  mode:    M.c.p.  type  2339,  flashing 

LED.   

NOTE!

   This  mode  is  only  used 

for backwards compatibility. 

 

2312

  mode:    M.c.p.  type  2339,  non-

flashing  LED.   

NOTE!

    This  mode  is 

only used for backwards compatibility. 

Two  flying  leads  (wires)  are  connected  to 
the terminal  block  and  shall be  used for  the 
address setting tool's connection cable.  The 
wires shall be disconnected before the COM 
loop wires are connected. 

Product applications 

Used in the  systems  EBL512  /  128  / 1000 / 
2000  and  is  intended  for  indoor  use  in 
premises where IP56 rating is required. 