8

Address selector

If you are installing two indoor units in the same room and you
want them to operate in independent mode, it is necessary to
assign each unit its own address so that each unit can operate
via its own remote control.
For configuration, proceed as follows:

Configuration (unit address) Table I

• Press the 

 and 

 buttons of the infrared remote control and

hold them pressed for more than 5 seconds.

• The display will be cleared, the time segments will display the

first configuration item (rAdr = remote address) and the tempera-
ture segments will display the default value of this configuration
item (Ab = control of both indoor units).

• Press either the 

 or 

 button to change the default value (Ab)

to the new value (A) or (b).

• Press 

 button to transmit the new configuration to the unit.

• Press 

 button to leave the configuration menu.

Configuration (remote control address) Table II

• Press the 

 and 

 buttons of the infrared remote control and

hold them pressed for more than 5 seconds.

• The display will be cleared, the temperature segments will

display the first configuration item (CH = remote address) and
the time segments will display the default value of this
configuration item (Ab = control of both indoor units).

• Press either the 

 or 

 button to change the default value (Ab)

to the new value (A) or (b).

• Press 

 button to set the new configuration on the remote

control.

• Press 

 button to leave the configuration menu.

Note:
When 30 seconds have elapsed and no buttons have been
pressed, the remote control will automatically exit the
configuration menu and the procedure has to be restarted.

Fault code for 40SMC---N

When a fault code is detected while the indoor unit is working,
the green LED of the unit starts to blink every 0.5 seconds.
The alarm code can be drawn by the number of times the LED
blinks and stops the unit.
5 seconds elapse between one series of blinks and the next.

Table  III: fault code 40SMC---N

Code

Alarm description

Resetting

2

Condensate discharge pump

No

3

Air sensor

Yes

4

Indoor coil sensor

Yes

5

Not used

Yes

6

Dirty filter

Yes

7

Outdoor unit malfunction

Yes

8

Low voltage limit

Yes

9

Compressor malfunction

Yes

 

(for 4 consecutive times)

10

EEprom memory damaged

Yes

11

Serial number not valid

Yes

12

Address / unit zone not valid

Yes

13

Not used

Yes

Fault code for 40SQV

The inside unit can detect any system fault and stop it at once.
The failure is recoverable based on the table VI below.
When a diagnostic is active, the  green LED (P) and the yellow
LED (R) blink 0.1 seconds on, 0.1 seconds off and indicate a
fault code.
The yellow LED (R) indicates  the tens digits.
The green LED (P) indicates the unit digits.
Two seconds elapse between the yellow LED and the green
LED lighting.
The sequence ends with both LEDs off for 4 seconds.

Example:
Fault code 12

• The yellow LED blinks (it indicates the tens digits).
• Both LEDS are off for 2 seconds.
• The green LED blinks twice with a 0,5 seconds frequency.
• Both LEDS are off for 4 seconds.

The fault sequence described above is repeated until the fault
has been repaired.
If the fault code is lower than 10, the yellow LED (R) is not
blinking.

Table VI: fault code 40SQV

Code Description

2

Condensate Pump Failure or water drain Failure

3

Indoor unit Room Air sensor fault

4

Indoor unit Tc Coil sensor fault

10

Indoor unit software fault (EEProm Corrupt)

12

Indoor unit software fault (Address / Zone Corrupt)

14

Loss of Signal From CDU

15

Indoor unit Tcj Coil sensor fault

18

Outdoor unit control box fault (G-Tr short circuit protection)

20

Position Detection Circuit Error

21

Outdoor unit Current Sensor fault

22

Outdoor unit Heat Exchange Sensor fault

23

Outdoor unit Discharge Temperature Sensor fault

24

Outdoor unit Fan fault

26

Other Outdoor unit fault

27

Outdoor unit Compressor Lock

28

Outdoor unit Discharge Temperature fault

29

Outdoor unit Compressor Breakdown

31

Outdoor unit High Temperature/Pressure Release

For the fault codes of the outdoor unit please refer to Installation
manual of 38VYX not available for the size 050.
In case of malfunction, record the fault code, turn the system off,
disconnect the mains power supply and contact a qualified
service
engineer.

My-comfort control

Address selector, fault code and guide for the owner

E N G L I S H

Guide for the owner

When installation and tests are completed explain the Operation
and Maintenance Manual to the owner, with particular attention to
the main operating modes of the air conditioner, such as:

• Turning the unit on and off.

• Functions of the remote control.

Leave the two installation manuals for the indoor and outdoor units
with the owner for future use during maintenance operations or for
any other needs.

Summary of Contents for 40SMC N Series

Page 1: ...rnbedienung seite 15 17 ACONDICIONADORES DE AIRE Instrucciones SISTEMA SPLIT Satellite Mando a distancia de infrarrojos p g 18 20 SPLIT SYSTEMEN Instructies Afstandsbediening KLIMAATREGELAARS Satellit...

Page 2: ...ponents fig page 1 Componenti del kit fig pag 1 Composants du kit fig page 1 Komponenten des Satzes Abb Seite 1 Componentes del kit fig p g 1 DESCRIPTION DESCRIZIONE DESCRIPTION BESCHREIBUNG DESCRIPCI...

Page 3: ...3 5 40SMC N 40SQV 15 m 7 6 15 m max 30 m max 15 m max 15 m max...

Page 4: ...4 9 40SMC N 40SQV 8 10 11...

Page 5: ...5 40SMC N 40SQV 12...

Page 6: ...e and buttons of the infrared remote control and hold them pressed for more than 5 seconds The display will be cleared the temperature segments will display the first configuration item CH remote addr...

Page 7: ...completed During the test the indoor fan works at high speed and the outdoor fan changes its speed every 30 seconds from high to low while the electric heaters are off The test could stop for the foll...

Page 8: ...ss unit zone not valid Yes 13 Not used Yes Fault code for 40SQV The inside unit can detect any system fault and stop it at once The failure is recoverable based on the table VI below When a diagnostic...

Page 9: ...apparir senza icone il segmento della temperatura mostrer la prima voce di configurazione CH indirizzo remoto e il segmento dell orario mostrer il valore predefinito di questa configurazione Ab contr...

Page 10: ...alta velocit il ventilatore esterno cambier la sua velocit ogni 30 secondi passando dall alta alla bassa e le resistenze elettriche saranno spente Ognuna delle successive azioni avr l effetto di term...

Page 11: ...re il malfunzionamento del sistema arrestandolo immediatamente La causa del guasto pu essere individuata consultando la tabella VI riportata qui sotto Con la diagnostica attiva i led verde P e giallo...

Page 12: ...ches et de la t l commande infrarouge et les maintenir enfonc es pendant plus de 5 secondes L affichage est remis z ro les segments de temp rature affichent le premier l ment de configuration CH adres...

Page 13: ...marche haute vitesse le ventilateur ext rieur change sa vitesse toutes les 30 secondes en passant de la haute la basse vitesse et les r sistances lectriques restent teintes Chacune des op rations suiv...

Page 14: ...utilis Oui Code de d faut pour 40SQV L unit int rieure d tecte le dysfonctionnement du syst me en l arr tant tout de suite La cause de la panne peut tre identifi e en consultant le tableau VI ci apr...

Page 15: ...ese ausgeschaltet lassen Die Tasten und der Fernbedienung dr cken und 5 Sekunden lang gedr ckt halten Die Anzeige wird gel scht die Temperatursegmente zeigen den Vorgabewert dieses Konfigurationposten...

Page 16: ...le 30 Sekunden von hoher zu niedriger Geschwindigkeit die elektrische Widerst nde sind ausgeschaltet In allen folgenden F lle wird der Test beendet Taste ON OFF wird gedr ckt Stromversorgung f llt aus...

Page 17: ...sofort zu stoppen Die St rungsursache kann aus der hier unten angef hrten Tabelle VI gelesen werden Ist die Diagnostik aktiv blinken die gr ne Led P und die gelbe Led R alle 0 5 Sekunden und zeigen ei...

Page 18: ...rrojos Se borrar la pantalla y los segmentos de tiempo mostrar n el primer elemento de la configuraci n CH direcci n remota y los segmentos de temperatura mostrar n el valor por defecto de este primer...

Page 19: ...r interno girar a la alta velocidad el ventilador externocambiar su velocidad cada 30 segundos pasando de la alta a la baja y las resistencias el ctricas estar n apagadas Cada una de las siguientes ac...

Page 20: ...to y Mantenimiento prestando especial atenci n a los principales modos de funcionamiento de la unidad como se citan a continuaci n Como encender y apagar la unidad Funciones del control remoto Dejar a...

Page 21: ...atterijen in de afstandbediening maar laat hem UIT Houd de toetsen en van de afstandbediening gelijktijdig langer dan 5 seconden ingedrukt In de display wordt het eerste configuratie item afgebeeld CH...

Page 22: ...ole draait de binnenventilator op hoge snelheid de buitenventilator wijzigt zijn snelheid iedere 30 seconden met overgang van de hoge naar de lage snelheid terwijl de elektrische weerstanden uitgescha...

Page 23: ...RLANDS Foutcode voor 40SQV De binnen unit is in staat de storing van het systeem waar te nemen en het onmiddellijk af te zetten De oorzaak van het defect kan met behulp van de hieronder gegeven tabel...

Page 24: ...AC II 30 12345 1 J rc HP AC HR CR 6 II 7 38 A A I A CH b B I B Ab J X tU C C 0 F Z C rc HPQ ACQ J HR 17 32 17 C 32 C C C 63 90 63 F 90 F C Z CR 17 32 17 C 32 C C C 63 90 63 F 90 F C Z CL 12 12 12 AM Q...

Page 25: ...C N OFF 5 0 Src 1 1 3 2 J J Q Q 3 2 40 C Q MULTISPLIT J LED 2 0 5 0 5 5 Q VRF 4 Q CD 3 Q MULTI 2 5 3 2 J 40 C C 30 C ON OFF I J 30 0 60 C 30 6 40SQV OFF 5 0 Src P R 2 C 3 3 0 3 40 C Q 1 3 C 2 3 J Q 30...

Page 26: ...40SMC N 6 8 6 2 J 3 J 4 J 5 I 6 J 7 G 8 9 G 4 10 l EEprom 11 I 12 I 13 I 6 40SQV VI P R 0 5 R P 2 Q 4 C 12 2 0 5 4 Q 10 R 6 VI 6 40SQV 6 2 X 3 X 4 X 10 X EEProm 12 X I X 14 J CDU 15 X 18 X G Tr 20 Q 2...

Page 27: ...remoto por infravermelhos e mantenham nos pressionados durante mais 5 segundos O visor ficar limpo os segmentos do tempo apresentar o o primeiro item da configura o CH endere o remoto e os segmentos d...

Page 28: ...o virar em alta velocidade o ventilador externo mudar a sua velocidade a cada 30 segundos passando de alta a baixa e as resist ncias el ctricas ser o desligadas Cada uma das ac es seguintes ter o efei...

Page 29: ...amente A causa da avaria pode ser identificada consultando a tabela VI reproduzida abaixo Com o diagn stico ativo os leds verde P e amarelo R iniciam a lampejar em intervalos de 0 5 segundos indicando...

Page 30: ...ngd OFF Tryck ned och knapparna p den infrar da fj rrkontrollen och h ll dem nedtryckta l ngre n 5 sekunder Displayen rensas i temperaturf lten visas den f rsta konfigurationsfunktionen CH extern adre...

Page 31: ...en externa ventilatorn byter hastighet vart 30 sekund medan den byter fr n h gt till l gt l ge och de elektriska motst nden r avst ngda Var och en av f ljande g rningar avslutar testet Tryck av ON OFF...

Page 32: ...Ja 13 Ej anv nd Ja Felkoder 40SQV Inomhusenheten r i st nd att k nna av felfunktion p systemet och stoppa systemet omedelbart Orsaken till felet kan fastst llas med hj lp av tabellen VI nedan Med akt...

Page 33: ...t kaukos timeen ja j t se OFF tilaan Paina ja pid painettuna ja painikkeet infrapunakaukos timess yli 5 sekuntia N ytt on oltava tyhj l mp tilalohko n ytt ensimm isen ohjelmointiosan CH poista osoite...

Page 34: ...en tuuletin toimii nopealla nopeudella ja ulkoinen tuuletin vaihtaa nopeuttaan joka 30 sekunti siirtyen nopeasta hitaaseen nopeuteen ja s hk vastukset sammutetaan Testi p ttyy seuraavien toimenpiteide...

Page 35: ...k voi keskeytt j rjestelm n toimintah iri n pys ytt m ll j rjestelm n v litt m sti Vian syy voidaan selvitt alla olevan taulukon VI avulla Vianetsinn n ollessa aktiivinen vihre ledi P ja keltainen led...

Page 36: ...uit peut n cessiter des modifications ou changements sans pr avis nderungen im Zuge der technischen Weiterentwicklung vorbehalten El fabricante se reserva el derecho de cambiar algunas especificacione...

Reviews: