background image

21

SERVICE

Refrigeration System

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in damage to

equipment.
This system uses Puron

R

refrigerant which has higher

pressures than R-22 and other refrigerants. No other

refrigerant may be used in this system. Gage set,

hoses, and recovery system must be designed to

handle Puron. If you are unsure consult the equipment

manufacturer.

CAUTION

!

Compressor Oil —

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in damage to

equipment.
The compressor in a Puron system uses a polyolester

(POE) oil. This oil is extremely hygroscopic, meaning

it absorbs water readily. POE oils can absorb 15 times

as much water as other oils designed for HCFC and

CFC refrigerants. Take all necessary precautions to

avoid exposure of the oil to the atmosphere.

CAUTION

!

Servicing Systems on Roofs With Synthetic Materials —

POE (polyolester) compressor lubricants are known to cause

long term damage to some synthetic roofing materials.

Exposure, even if immediately cleaned up, may cause

embrittlement (leading to cracking) to occur in one year or

more. When performing any service which may risk

exposure of compressor oil to the roof, take appropriate

precautions to protect roofing. Procedures which risk oil

leakage include but are not limited to compressor

replacement,

repairing

refrigerants

leaks,

replacing

refrigerant components such as filter drier, pressure switch,

metering device, coil, accumulator, or reversing valve.

Synthetic Roof Precautionary Procedure:

1. Cover extended roof working area with an imper-

meable polyethylene (plastic) drop cloth or tarp.

Cover an approximate 10 x 10 ft (3.3 x 3.3 m) area.

2. Cover area in front of the unit service panel with a

terry cloth shop towel to absorb lubricant spills and

prevent run-offs, and protect drop cloth from tears

caused by tools or components.

3. Place terry cloth shop towel inside unit immediately un-

der component(s) to be serviced and prevent lubricant

run-offs through the louvered openings in the base pan.

4. Perform required service.
5. Remove and dispose of any oil contaminated material

per local codes.

Liquid Line Filter Drier —

The factory-provided filter drier is specifically designed to

operate with Puron

. Replace the filter drier with

factory-authorized components only with a filter drier

with desiccant made from 100% molecular sieve grade

XH-11. Filter drier must be replaced whenever the

refrigerant system is opened.

When removing a filter drier, use a tubing cutter to cut the

drier from the system.

Do not unsweat a filter drier

from

the system. Heat from unsweating will release moisture

and contaminants from drier into system.

Field Refrigerant Access Ports —

Field service access to refrigerant pressures is through the

access ports located at the service valves (see Fig. 24).

These ports are

-in SAE Flare couplings with Schrader

check valves and service caps. Use these ports to admit

nitrogen to the field tubing during brazing, to evacuate the

tubing and evaporator coil, to admit initial refrigerant

charge into the low-side of the system and when checking

and adjusting the system refrigerant charge. When service

activities are completed, ensure the service caps are in

place and secure; check for leaks. If the Schrader check

valve must be removed and re-installed, tighten to 2-3

in-lbs (23-34 N-cm).

Factory High-Flow Access Ports —

There are two additional access ports in the system - on

the suction tube between the compressor and the suction

service valve and on the liquid tube near the liquid service

valve (see Fig. 25). These are brass fittings with black

plastic caps. The hose connection fittings are standard

-in SAE Male Flare couplings.

The brass fittings are two-piece High Flow valves, with a

receptacle base brazed to the tubing and an integral

spring-closed check valve core screwed into the base. (See

Fig. 21) This check valve is permanently assembled into

this core body and cannot be serviced separately; replace

the entire core body if necessary. Service tools are

available from RCD that allow the replacement of the

check valve core without having to recover the entire

system refrigerant charge. Apply compressor refrigerant

oil to the check valve core’s bottom o-ring. Install the

fitting body with 96

-10 in-lbs (1085

23 N-cm) of

torque; do not overtighten.

38A

U

Summary of Contents for 38AUZ

Page 1: ...arge 16 START UP 16 19 Preliminary Checks 16 Start Unit 17 OPERATING SEQUENCE 20 Base Unit Controls 20 Indoor Supply Fan 20 Cooling Unit Without Economizer 20 Cooling Unit with Economizer 20 Heating 2...

Page 2: ...th WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE i...

Page 3: ...0 Not Used 3 Example 8 A U Z D 0 8 A 0 A 6 A 0 A 0 A 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Packaging 0 Standard 1 LTL Electrical Options A None C Non Fused Disconnect Service Options 0 None 1...

Page 4: ...CORNER A CORNER B CORNER C CORNER D CENTER OF GRAVITY UNIT HEIGHT lbs kg lbs kg lbs kg lbs kg lbs kg X Y Z H 38AUZD E08 430 195 142 64 96 44 76 34 111 50 18 457 24 610 21 533 42 3 8 1076 Fig 2 38AUZD...

Page 5: ...ge only Typical operating charge with 25 ft of interconnecting piping Table 2 Physical Data 38AUZD E08 60 Hz SI NOMINAL CAPACITY kW 26 4 OPERATING WEIGHTS lb Round Tube Plate Fin Coil Cu Al 195 REFRIG...

Page 6: ...requirements outdoor unit above indoor unit liquid line lift outdoor unit below indoor unit and hot gas bypass line Relocate sections to minimize the length of interconnecting tubing DO NOT BURY REFRI...

Page 7: ...ine equivalent line length adjustments for path and components and add to linear line lengths See Table 4 Equivalent Lengths for Common Fittings for usual fitting types Also identify adjustments for r...

Page 8: ...lift requirement Suction Riser A suction riser condition exists when the outdoor unit is located above the indoor evaporator unit and suction vapor must flow vertically up to return to the compressor...

Page 9: ...uid Line Solenoid Valve Many older unit designs included automatic capacity controls that sensed changes in suction pressure and could increase or decrease compressor capacity automatically as the eva...

Page 10: ...38AU circuit through the liquid service valve s The amount of refrigerant added must be at least 80 of the operating charge listed in Table 3 for LINEAR line length LESS the factory charge quantity if...

Page 11: ...n points Make field power connections directly to line connection pressure lugs only FIRE HAZARD Failure to follow this warning could cause in personal injury death and or equipment damage Do not conn...

Page 12: ...t is to be connected to a 208 v power supply the control transformer must be rewired by moving the black wire with the in female spade connector from the 230 v connection and moving it to the 208 v in...

Page 13: ...GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip...

Page 14: ...mfort Network or as a stand alone control Thermostat Install a Carrier approved accessory thermostat according to installation instructions included with the accessory Locate the thermostat accessory...

Page 15: ...ONNECT SIZE MIN MAX RLA LRA QTY FLA MCA MOCP FLA LRA 38AUZD E08 208 230 3 60 187 253 24 0 186 2 1 5 33 50 31 192 460 3 60 414 506 12 6 100 2 0 8 18 25 16 104 575 3 60 518 633 9 9 78 2 0 6 14 20 13 82...

Page 16: ...oint above the space temperature so there is no demand for cooling 2 Close the field disconnect Preliminary Charge Before starting the unit charge liquid refrigerant into the high side of the system t...

Page 17: ...ced Scroll Temperature Protection Label 0 10 20 30 40 50 60 70 80 90 100 110 120 0 10 20 30 40 60 70 80 90 50 Compressor Unloaded Run Time Minutes Times are approximate NOTE Various factors including...

Page 18: ...70 90 110 130 150 140 190 240 290 340 390 440 490 540 590 PRESSURE AT LIQUID VALVE PSIG PRESSION LA VANNE DE LIQUIDE PSIG 7 5 TON DUAL STAGE CHARGING CHART PURON COMPRESSOR FULL LOAD ALL CONDENSER FAN...

Page 19: ...19 C14294 Fig 20 Typical 38AUZD E08 Wiring Diagram 208 230V 3PH 60Hz Unit Shown 38AU...

Page 20: ...id line solenoid is de energized valve closes CADM initiates a TRIP event cooling demand sensed at CADM terminal Y but no current is measured at T1 T2 T3 motor sensors CADM relay opens and RED LED is...

Page 21: ...e and dispose of any oil contaminated material per local codes Liquid Line Filter Drier The factory provided filter drier is specifically designed to operate with Puron Replace the filter drier with f...

Page 22: ...he CADM The ALERT LED indicates an abnormal condition exists in the system through a flash code The ALERT LED will blink a number of times consecutively pause and the repeat the process The number of...

Page 23: ...ning c Evaporator coil is frozen d Faulty metering device e Condenser coil is dirty f Liquid line restriction filter drier blocked if present Yellow ALERT Flash Code 3 Short Cycling Compressor is runn...

Page 24: ...nt If not R and C are reverse wired Verify voltage at contactor coil falls below 0 5VAC when off Compressor Protection Compressor Overtemperature Protection IP A thermostat installed on the compressor...

Page 25: ...25 Condenser Fans Service Valves C14295 Fig 24 38AUZD E08 Exterior Outdoor Coil 32LT Sensor Typical Location HPS LPS High Flow Access Port C14296 Fig 25 38AUZD E08 Interior 38AU...

Page 26: ...lt in reduced unit performance High velocity water from a pressure washer garden hose or compressed air should never be used to clean a coil The force of the water or air jet will bend the fin edges a...

Page 27: ...ive 5 Reset lockout circuit 6 Low pressure switch open 6 Check for refrigerant undercharge obstruction of indoor airflow Make sure liquid line solenoid valve s is open 7 High pressure switch open 7 Ch...

Page 28: ...lace filters 4 Expansion valve power head defective 4 Replace power head 5 Indoor coil partially iced 5 Check low pressure setting 6 Indoor airflow restricted 6 Remove obstruction Suction Pressure Hig...

Page 29: ...ll filter driers and service valves with wet cloth when brazing S A factory approved liquid line filter drier is required on every unit S Do not use an R 22 TXV S If indoor unit is equipped with a TXV...

Page 30: ...t power wires Troubleshooting OBSERVATION POSSIBLE REMEDY Fans won t start All fans Check power wiring Check outdoor fan relay OFR OFM1 OFM3 only Check speed control sensor location Check speed sensor...

Page 31: ...31 D K J H G F E C B A C10800 Fig 28 Wind Baffles 38AU...

Page 32: ...4 25 1 4 33 1 4 BACK 40 40 3 4 41 1 2 35 1 4 4 1 4 11 1 4 18 1 4 25 1 4 32 1 4 RIGHT SIDE 25 25 1 2 26 1 4 35 1 4 4 1 4 11 1 4 18 1 4 25 1 4 32 1 4 DIMENSIONS MM UNIT BAFFLE A B C D E F G H J K 38AUZ...

Page 33: ...33 38AU...

Page 34: ...cturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53380040 01 Printed in U S A Form 38AUZD E08 02S...

Page 35: ...ALL WIRING TERMINALS including main power supply TIGHT Y N HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS Y N INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ARE PROPE...

Page 36: ...D THE FOLLOWING MEASUREMENTS SUCTION PRESSURE SUCTION LINE TEMP LIQUID PRESSURE LIQUID LINE TEMP ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB dry bulb TEMP...

Reviews: