background image

9

Table 6 – Refrigerant Specialties Part Numbers

LIQUID LINE

SIZE (in.)

LIQUID LINE

SOLENOID VALVE (LLSV)

LLSV

COIL

SIGHT

GLASS

FILTER

DRIER

1

/

2

EF680035

EF680037

KM680004

KH43LS085

5

/

8

EF680036

EF680037

KM680005

KH43LS087

Check 38AUZD/E08 Model with Evaporator Coil

Connections —

Confirm before installation of unit that the evaporator coil

connections are consistent with the 38AUZD/E08.

Insulate Suction Lines —

Apply closed-cell tubular insulation to all suction lines

between evaporator coil connection and 38AUZD/E08

unit’s suction service valve.

Refer to Table 6 for recommendations on refrigeration

specialties.
Select the filter drier for maximum unit capacity and

minimum pressure drop. Complete the refrigerant piping

from the indoor unit to the outdoor unit before opening

the liquid and suction lines at the outdoor unit.

Install Liquid Line Solenoid Valve —

It is recommended that a solenoid valve be placed in the

main liquid line (see Fig. 6) between the condensing unit

and the evaporator coil. Locate the solenoid valve at the

outlet end of the liquid line, near the evaporator coil

connections, with flow direction arrow pointed at the

evaporator coil. Refer to Table 6. (A liquid line solenoid

valve is required when the liquid line length exceeds 75 ft

[23 m].) This valve prevents refrigerant migration (which

causes oil dilution) to the compressor during the off cycle, at

low outdoor ambient temperatures. Wire the solenoid in

parallel with the compressor contactor coil (see Fig. 6). This

means of electrical control is referred to as solenoid

drop

control.

Single Circuit Coil Piping Configuration

For single compressor condensing units

15 DIAMS

MIN

10

DIAMS

8 DIAMS

MIN

INDOOR

COIL CKT

AIRFLOW

TXV

SENSING

BULB

EQUALIZER LINE

SIGHT GLASS

A  LOCATION

TXV

FILTER DRIER

A  LOCATION

LIQUID LINE

SOLENOID

VALVE

FLOW

C14291

Fig. 6 -- Location of Sight Glass and Filter Drier

Solenoid drop control wiring:

Control the power to the

liquid line solenoid through a Solenoid Valve Relay (SVR)

in all units. Use part number HN61PC005 (field--supplied,

installed). 38AUZD/E08 unit requires one SVR.

Evaporator Capacity Control Liquid Line Solenoid

Valve:

Many older unit designs included automatic

capacity controls that sensed changes in suction pressure

and could increase or decrease compressor capacity

automatically as the evaporator load changed. Control

systems were used on these units that had the thermostat’s

second stage contacts control a capacity control liquid line

solenoid valve to open or shutoff a portion of the

evaporator surface without any direct connection to the

compressor circuit.

This form of system capacity staging control is not

possible with 38AU models. If this installation is a retrofit

for a unit that included automatic pressure--operated

unloading, check the existing thermostat and liquid

solenoid valve.

When found, convert the evaporator

second stage solenoid control into a drop--solenoid

control.

Selecting an Accumulator –

Because all 38AU models use scroll compressors, an

accumulator is not required. If an accumulator is to be

added, check the accumulator manufacturer’s literature

carefully for indication of its suitability for use with

R--410A; look for minimum working pressure of 200 psig

(1380 kPa). Select the accumulator first on the basis of its

cataloged minimum capacity (tons) to ensure oil return from

the accumulator, then on tube size or holding capacity.

Make Piping Connections —

Piping connections at the 38AUZ unit are ball valves with

stub tube extensions. Do not open the unit service valves

until all interconnecting tube brazing has been completed.

The stub tube connections include

1

/

4

-in SAE service fittings

with Schrader valve cores (see Fig. 7). Before making any

brazed connections to the unit service valves, remove both

Schrader valve caps and cores and save for re-installation.

Connect a source for nitrogen to one of these service fittings

during tube brazing to prevent the formation of copper

oxides inside the tubes at brazed joints.

When connecting the field tubing to the 38AUZ service

valves, wrap the valves in wet rags to prevent overheating.

Pressure-test all joints from outdoor unit connections over

to the evaporator coil, using nitrogen as pressure and with

soap-and-bubbles.

When pressure-testing is completed, remove the nitrogen

source at the outdoor unit service valves and re-install the

two Schrader valve cores. Torque the cores to 2-3 in-lbs

(23-34 N-cm).

38A

U

Summary of Contents for 38AUZ

Page 1: ...arge 16 START UP 16 19 Preliminary Checks 16 Start Unit 17 OPERATING SEQUENCE 20 Base Unit Controls 20 Indoor Supply Fan 20 Cooling Unit Without Economizer 20 Cooling Unit with Economizer 20 Heating 2...

Page 2: ...th WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE i...

Page 3: ...0 Not Used 3 Example 8 A U Z D 0 8 A 0 A 6 A 0 A 0 A 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Packaging 0 Standard 1 LTL Electrical Options A None C Non Fused Disconnect Service Options 0 None 1...

Page 4: ...CORNER A CORNER B CORNER C CORNER D CENTER OF GRAVITY UNIT HEIGHT lbs kg lbs kg lbs kg lbs kg lbs kg X Y Z H 38AUZD E08 430 195 142 64 96 44 76 34 111 50 18 457 24 610 21 533 42 3 8 1076 Fig 2 38AUZD...

Page 5: ...ge only Typical operating charge with 25 ft of interconnecting piping Table 2 Physical Data 38AUZD E08 60 Hz SI NOMINAL CAPACITY kW 26 4 OPERATING WEIGHTS lb Round Tube Plate Fin Coil Cu Al 195 REFRIG...

Page 6: ...requirements outdoor unit above indoor unit liquid line lift outdoor unit below indoor unit and hot gas bypass line Relocate sections to minimize the length of interconnecting tubing DO NOT BURY REFRI...

Page 7: ...ine equivalent line length adjustments for path and components and add to linear line lengths See Table 4 Equivalent Lengths for Common Fittings for usual fitting types Also identify adjustments for r...

Page 8: ...lift requirement Suction Riser A suction riser condition exists when the outdoor unit is located above the indoor evaporator unit and suction vapor must flow vertically up to return to the compressor...

Page 9: ...uid Line Solenoid Valve Many older unit designs included automatic capacity controls that sensed changes in suction pressure and could increase or decrease compressor capacity automatically as the eva...

Page 10: ...38AU circuit through the liquid service valve s The amount of refrigerant added must be at least 80 of the operating charge listed in Table 3 for LINEAR line length LESS the factory charge quantity if...

Page 11: ...n points Make field power connections directly to line connection pressure lugs only FIRE HAZARD Failure to follow this warning could cause in personal injury death and or equipment damage Do not conn...

Page 12: ...t is to be connected to a 208 v power supply the control transformer must be rewired by moving the black wire with the in female spade connector from the 230 v connection and moving it to the 208 v in...

Page 13: ...GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip...

Page 14: ...mfort Network or as a stand alone control Thermostat Install a Carrier approved accessory thermostat according to installation instructions included with the accessory Locate the thermostat accessory...

Page 15: ...ONNECT SIZE MIN MAX RLA LRA QTY FLA MCA MOCP FLA LRA 38AUZD E08 208 230 3 60 187 253 24 0 186 2 1 5 33 50 31 192 460 3 60 414 506 12 6 100 2 0 8 18 25 16 104 575 3 60 518 633 9 9 78 2 0 6 14 20 13 82...

Page 16: ...oint above the space temperature so there is no demand for cooling 2 Close the field disconnect Preliminary Charge Before starting the unit charge liquid refrigerant into the high side of the system t...

Page 17: ...ced Scroll Temperature Protection Label 0 10 20 30 40 50 60 70 80 90 100 110 120 0 10 20 30 40 60 70 80 90 50 Compressor Unloaded Run Time Minutes Times are approximate NOTE Various factors including...

Page 18: ...70 90 110 130 150 140 190 240 290 340 390 440 490 540 590 PRESSURE AT LIQUID VALVE PSIG PRESSION LA VANNE DE LIQUIDE PSIG 7 5 TON DUAL STAGE CHARGING CHART PURON COMPRESSOR FULL LOAD ALL CONDENSER FAN...

Page 19: ...19 C14294 Fig 20 Typical 38AUZD E08 Wiring Diagram 208 230V 3PH 60Hz Unit Shown 38AU...

Page 20: ...id line solenoid is de energized valve closes CADM initiates a TRIP event cooling demand sensed at CADM terminal Y but no current is measured at T1 T2 T3 motor sensors CADM relay opens and RED LED is...

Page 21: ...e and dispose of any oil contaminated material per local codes Liquid Line Filter Drier The factory provided filter drier is specifically designed to operate with Puron Replace the filter drier with f...

Page 22: ...he CADM The ALERT LED indicates an abnormal condition exists in the system through a flash code The ALERT LED will blink a number of times consecutively pause and the repeat the process The number of...

Page 23: ...ning c Evaporator coil is frozen d Faulty metering device e Condenser coil is dirty f Liquid line restriction filter drier blocked if present Yellow ALERT Flash Code 3 Short Cycling Compressor is runn...

Page 24: ...nt If not R and C are reverse wired Verify voltage at contactor coil falls below 0 5VAC when off Compressor Protection Compressor Overtemperature Protection IP A thermostat installed on the compressor...

Page 25: ...25 Condenser Fans Service Valves C14295 Fig 24 38AUZD E08 Exterior Outdoor Coil 32LT Sensor Typical Location HPS LPS High Flow Access Port C14296 Fig 25 38AUZD E08 Interior 38AU...

Page 26: ...lt in reduced unit performance High velocity water from a pressure washer garden hose or compressed air should never be used to clean a coil The force of the water or air jet will bend the fin edges a...

Page 27: ...ive 5 Reset lockout circuit 6 Low pressure switch open 6 Check for refrigerant undercharge obstruction of indoor airflow Make sure liquid line solenoid valve s is open 7 High pressure switch open 7 Ch...

Page 28: ...lace filters 4 Expansion valve power head defective 4 Replace power head 5 Indoor coil partially iced 5 Check low pressure setting 6 Indoor airflow restricted 6 Remove obstruction Suction Pressure Hig...

Page 29: ...ll filter driers and service valves with wet cloth when brazing S A factory approved liquid line filter drier is required on every unit S Do not use an R 22 TXV S If indoor unit is equipped with a TXV...

Page 30: ...t power wires Troubleshooting OBSERVATION POSSIBLE REMEDY Fans won t start All fans Check power wiring Check outdoor fan relay OFR OFM1 OFM3 only Check speed control sensor location Check speed sensor...

Page 31: ...31 D K J H G F E C B A C10800 Fig 28 Wind Baffles 38AU...

Page 32: ...4 25 1 4 33 1 4 BACK 40 40 3 4 41 1 2 35 1 4 4 1 4 11 1 4 18 1 4 25 1 4 32 1 4 RIGHT SIDE 25 25 1 2 26 1 4 35 1 4 4 1 4 11 1 4 18 1 4 25 1 4 32 1 4 DIMENSIONS MM UNIT BAFFLE A B C D E F G H J K 38AUZ...

Page 33: ...33 38AU...

Page 34: ...cturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53380040 01 Printed in U S A Form 38AUZD E08 02S...

Page 35: ...ALL WIRING TERMINALS including main power supply TIGHT Y N HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS Y N INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ARE PROPE...

Page 36: ...D THE FOLLOWING MEASUREMENTS SUCTION PRESSURE SUCTION LINE TEMP LIQUID PRESSURE LIQUID LINE TEMP ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB dry bulb TEMP...

Reviews: