Operation & Service Manual
Carrier Transicold Europe
31/03/07
Viento - Installation/Rev- #54/54
1. Connect manifold to evaporator outlet fitting.
2. Install a sensor on the expansion valve bulb location.
3. Run the unit on
COOLING
mode.
4. Correct superheat:
Turn anti-clockwise to increase flow & decrease
superheat
Turn clockwise to decrease flow and increase
superheat.
TXV adjustment
Viento 200
Viento 300
Viento 350
8°C at box temperature 0°C
(14.4°F at box T° : 32°F)
4°C at box temperature -20°C
(7.2°F at box T° : -4°F)
Installation Commissioning Settings TXV
setting