Operation & Service Manual
Carrier Transicold Europe
31/03/07
Viento - Installation/Rev- #24/54
Right installation
Wrong installation
Do not twist or curve the hose.
Keep enough length to avoid length variation when the
pipes are under pressure.
Pipes length can vary between -2% to +4%.
Using elbows and fittings make easier installations,
assist accessibility and increase hoses/pipes life.
Always insure that minimum radius is respected. Provide
a radius as big as possible to avoid constriction.
Minimum curve radius
Module 6
80 mm
Module 8
95 mm
Module 10
110 mm
Module 12
130 mm
Installation Unit hoses
Mounting recommendations