50
WM5-96 Instruction Manual
Technical Specifications
(x) = available
(o) = not available
List of the variables that can be connected to:
Analogue outputs (all listed variables with the only exception of energies), alarm outputs (all listed variables with the only
exception of energies), pulse outputs (only energies), communication (all listed variables).
No. 1-phase
2-ph. 3-wire 3-ph. 4-wire 3-ph. 3-wire 3-ph. 4-wire
Notes
system
system
bal. (1 CT) unbal. sys.
unbal. sys.
1
V L1
x
x
x
o
x
2
V L2
o
x
x
o
x
3
V L3
o
o
x
o
x
4
V L-N sys
o
x
x
o
x
Sys = system
=
Σ
Σ
5
V L1-2
o
x
x
x
x
6
V L2-3
o
o
x
x
x
7
V L3-1
o
o
x
x
x
8
V L-L sys
o
o
x
x
x
Sys = system
=
Σ
Σ
9
A L1
x
x
x
x
x
10
A L2
o
x
x
x
x
11
A L3
o
o
x
x
x
12
An
o
x
x
o
x
An=neutral current
13
W L1
x
x
x
x
x
14
W L2
o
x
x
x
x
15
W L3
o
o
x
x
x
16
W sys
o
x
x
x
x
17
var L1
x
x
x
x
x
18
var L2
o
x
x
x
x
19
var L3
o
o
x
x
x
20
var sys
o
x
x
x
x
Sys = system
=
Σ
Σ
21
VA L1
x
x
x
x
x
22
VA L2
o
x
x
x
x
23
VA L3
o
o
x
x
x
24
VA sys
o
x
x
x
x
Sys = system
=
Σ
Σ
25
PF L1
x
x
x
x
x
26
PF L2
o
x
x
x
x
27
PF L3
o
o
x
x
x
28
PF sys
o
x
x
x
x
Sys = system
=
Σ
Σ
29
Hz
x
x
x
x
x
30
ASY VL-N
o
x
x
o
x
Asymmetry of phase-neutral
31
ASY VL-L
o
o
x
x
x
Asymmetry of phase-phase
32
THD V1
x
x
x
o
x
33
THD V2
o
x
x
o
x
34
THD V3
o
o
x
o
x
35
THD V1-2
o
x
x
x
x
36
THD V2-3
o
o
x
x
x
37
THD V3-1
o
o
x
x
x
38
THD A1
x
x
x
x
x
39
THD A2
o
x
x
x
x
40
THD A3
o
o
x
x
x
41
THDo V1
x
x
x
o
x
42
THDo V2
o
x
x
o
x
43
THDo V3
o
o
x
o
x
44
THDo V1-2
o
x
x
x
x
45
THDo V2-3
o
o
x
x
x
46
THDo V3-1
o
o
x
x
x
47
THDo A1
x
x
x
x
x
48
THDo A2
o
x
x
x
x
49
THDo A3
o
o
x
x
x
50
THDe V1
x
x
x
o
x
51
THDe V2
o
x
x
o
x
52
THDe V3
o
o
x
o
x
53
THDe V1-2
o
x
x
x
x
54
THDe V2-3
o
o
x
x
x
55
THDe V3-1
o
o
x
x
x
56
THDe A1
x
x
x
x
x
57
THDe A2
o
x
x
x
x
58
THDe A3
o
o
x
x
x
59
Phase seq.
o
o
x
x
x
Phase sequence
Summary of Contents for WM5-96 - PROGRAMMING
Page 1: ...WM5 96 Smart Power Quality Analyzer Instruction manual...
Page 2: ......
Page 12: ......
Page 54: ......