29
WM5-96 Instruction Manual
Programming WM5 96
This submenu allows the programming of the analog outputs (0-20mA,
0-10V, -5/+5mA). Select the function ANALOG OUTPUTS
(1)
by means
of the “
” and confirm with “S”. Then select the output to be pro-
grammed by means of the “
” keys
(2)
and confirm with “S”;
afterwards set the following parameters:
VARIABLE
(3)
: select the variable to be retransmitted by means of the
analog output. Choose the function “VARIABLE”
(3)
by means of the
“
” keys and confirm pressing the “S” key. Then select by the “
” keys the variable to be retransmitted (the list of the variables
depends on the selected system)
(3a)
then confirm with “S”.
MIN OUT
(3)
: set the value expressed as % of the output range (0-
20mA, 0-10V, -5/+5mA) to be coupled to the minimum measured
value. The instrument displays also the maximum and minimum value
which can be set (min, max). Select the function “MIN OUT” by means
of the “
” keys and confirm with “S”. Then set the value
(3b)
by
means of the “
” keys and confirm with “S”.
MAX OUT
(3)
: select
the value expressed as % of the output range (0-20mA, 0-10V, -
5/+5mA) to be coupled to the maximum measured value. The also
instrument displays the maximum and minimum value which can be
set (min, max). Select the MAX OUT function by means of the “
”
keys and confirm with “S”. Afterwards set the value (3c) by means of the
“
” keys and confirm with “S”.
MIN IN
(4)
: minimum value of the variable input range to which the
“MIN OUT” value, retransmitted by the analog output, will be coupled.
The instrument also displays the maximum and minimum value which
can be set (min, max) . Choose the function “MIN IN” by means of the
“
” keys and confirm with “S”. Then set the value
(4a)
by means
of the “
” keys, then confirm with “S”.
MAX IN
(4)
: maximum value of the variable input range to which the
“MAX OUT” value, retransmitted by the analog output, will be coupled.
The instrument also displays the maximum and minimum value which
can be set (min, max). Choose the MIN IN function by means of the
“
” and confirm with “S”. Then set the value
(4b)
by means of the
“
” keys and confirm with “S”.
Proceed, if possible, with the configuration of the other analog outputs
(up to a maximum of 8 outputs). To exit the menu “analog outputs”,
keep the “S” key pressed for at least 2 seconds.
Analog outputs
The instrument can manage the fol-
lowing analog outputs combinations:
Max n. 8 0-10VDC outputs; Max n.8
5/+5mADC outputs. Any combination of the
two above mentioned types considering that
each module manages up to 2 outputs. Max
n.4 0/20mADC outputs. Max n.4 0/20mADC
o max n.4 0-10VDC outputs.
************MMAAIINN MMEENNUU************
RREEVV.. 11..44..22..66 ((AAVV55))
DIGITAL OUTPUTS
ALARMS
EVENTS SELEC.
ANALOG OUTPUTS
****AANNAALLOOGG OOUUTTPPUUTT MMEENNUU**
OOUUTT AA00
VVAARRIIAABBLLEE:: VV11
VARIABLE
MIN OUT
MAX OUT
1
3
> 2s
a
****AANNAALLOOGG OOUUTTPPUUTT MMEENNUU**
OUT
A0
OUT
A1
OUT
B0
OUT B1
OUT
C0
V1
A1
W1
var1
****AANNAALLOOGG OOUUTTPPUUTT MMEENNUU**
OOUUTT AA00
MMAAXX IINN:: 00..000000
MAX OUT
MIN IN
MAX IN
4
a
MAX IN ?
0
.000
0.
min
-9999G
max
9999G
MIN IN ?
0
.000
0.
min
-9999G
max
9999G
2
3a
3c
3b
4b
4a
Measure
MIN OUT ?
0
.000
0.
min
-9999G
max
9999G
MAX OUT ?
0
.000
0.
min
-9999G
max
9999G