48 of 55
Digital variables
BMS Address
Description
Read/Write
Variable name
1
humidity sensor failure in zone 1
R
hum_sensor_fail_1
2 drain
status R
drain
3
bms on/off of the pump
R/W
Superv_OnOff
4
supply water valve status
R
WATER_ON
5
Global (general) alarm
R
GLOBAL_ALARM
6
high limit sensor failure alarm 1
R
hlimit_sensor_fail_1
7
airflow loss zone 1
R
airflow_al_1
8
high humidity in zone 1
R
hi_hum_al_1
9
low humidity in zone 1
R
lo_hum_al_1
10
stage1 of zone1 exceeded hours
R
run_hour_al_stg1_z1
11
stage2 of zone1 exceeded hours
R
run_hour_al_stg2_z1
12
stage3 of zone1 exceeded hours
R
run_hour_al_stg3_z1
13
stage4 of zone1 exceeded hours
R
run_hour_al_stg4_z1
14
stage5 of zone1 exceeded hours
R
run_hour_al_stg5_z1
15
stage6 of zone1 exceeded hours
R
run_hour_al_stg6_z1
16
humidity sensor failure in zone 1
R
hum_sensor_fail_2
17
bms on off for zone
R/W
bms_onoff_z_1
18
bms on off for zone
R/W
bms_onoff_z_2
19
bms on off for zone
R/W
bms_onoff_z_3
20
bms on off for zone
R/W
bms_onoff_z_4
21
bms on off for zone
R/W
bms_onoff_z_5
22
bms on off for zone
R/W
bms_onoff_z_6
23
bms on off for zone
R/W
bms_onoff_z_7
24
bms on off for zone
R/W
bms_onoff_z_8
25 alarm
reset
R/W
bms_res_all
26
bms on off for zone
R/W
bms_onoff_z_9
27
bms on off for zone
R/W
bms_onoff_z_10
28
bms on off for zone
R/W
bms_onoff_z_11
29
bms on off for zone
R/W
bms_onoff_z_12
30
high limit sensor failure alarm zone 2
R
hlimit_sensor_fail_2
31
airflow loss zone 2
R
airflow_al_2
32
high humidity in zone 2
R
hi_hum_al_2
33
low humidity in zone 2
R
lo_hum_al_2
34
stage1 of zone2 exceeded hours
R
run_hour_al_stg1_z2
35
stage2 of zone3 exceeded hours
R
run_hour_al_stg2_z3
36
stage2 of zone2 exceeded hours
R
run_hour_al_stg2_z2
37
stage3 of zone2 exceeded hours
R
run_hour_al_stg3_z2
38
stage4 of zone2 exceeded hours
R
run_hour_al_stg4_z2
39
stage5 of zone2 exceeded hours
R
run_hour_al_stg5_z2
40
stage6 of zone2 exceeded hours
R
run_hour_al_stg6_z2
41
humidity sensor failure in zone 3
R
hum_sensor_fail_3
42
high limit sensor failure alarm zone 3
R
hlimit_sensor_fail_3
43
airflow loss zone 3
R
airflow_al_3
Summary of Contents for humiFog UA1K0HM00
Page 1: ...humiFog UA pressure atomizing 1000 5000 kg hr READ AND SAVE THESE INSTRUCTIONS ...
Page 33: ...34 of 55 Fig 11 a 11 4 1 Replacement parts for the hydraulics and drive assembly ...
Page 34: ...35 of 55 Replacement parts for the electrical panel Fig 11 b ...
Page 38: ...39 of 55 FOR PUMPING STATIONS UA1K8H 000 UA2K5H 000 for voltage 66 SERIES TSF BRASS ...
Page 39: ...40 of 55 FOR PUMPING STATIONS UA1K0H 001 UA1K8H 001 UA2K5H 001 for voltage 66 SERIES TSF SS ...
Page 40: ...41 of 55 FOR PUMPING STATIONS UA3K5H 000 UA5K0H 000 for voltage Emperor HT Brass ...
Page 41: ...42 of 55 FOR PUMPING STATIONS UA3K5H 001 UA5K0H 001 for voltage PARTS LIST KEZ36A ...
Page 44: ...45 of 55 11 6 Wiring Schematic Figure 11 c ...
Page 52: ...53 of 55 NOTES ...
Page 53: ...54 of 55 NOTES ...