11 of 55
5. Plumbing
5.1
Water supply characteristics
The
humiFog
must be supplied exclusively with treated water according to the listed limit values. Under normal circumstances, this
means that the water must be treated with a Reverse Osmosis or Deionizer system.
Parameter
Symbol
Unit of measure
Limit
Min
Max
Ph
6.5
8.5
Specific conductivity
≅
20°C
σ
R, 20°C
µS/cm
0 50
Total hardness
TH mg/l
CaCO
3
0
25
Temporary hardness
mg/l
CaCO
3
0
15
Total dissolved solids
C
R
mg/l
(*)
(*)
Solid residue
≅
180°C
R
,180°C
mg/l
(*) (*)
Iron + manganese
mg/l Fe + Mn
0
0
Chlorides
ppm
Cl 0
10
Silicon di-oxide
mg/l
SiO
2
0
1
Chlorine ions
mg/l
Cl¯ 0
0
Calcium sulphate
mg/l
CaSO4
0
5
(*) Values depend on the water specific conductivity; usually: C
R
≅
0.65 *
σ
R, 20°C
;
R
,180°C
≅
0.9 *
σ
R, 20°C
WARNING:
If the specific conductivity is below 30, it is highly recommended to use the stainless steel
pump version of the pumping station.
Parameter
Unit of
measure
UA1K0*
UA1K8*
UA2K5*
UA3K5*
UA5K0*
Nominal pump flow
lt/hr / gpm
1000 / 4.4
1800 / 7.9
2500 / 11.0
3500 / 15.4
5000 / 22.0
Minimum supply flow
1
lt/hr / gpm
1250 / 5.5
2250 / 9.9
3136 / 13.8
4386 / 19.3
6250 / 27.5
Inlet Pressure
1
Mpa / Bar /
PSI
0.3-0.8 / 3-8 / 43-116
Temperature
º
C /
º
F
1-38 / 34-100
Inlet Connection
2
NPT
1” NPT Male
Minimum supply piping
1
NPT
1” NPT Male
1 1/2” NPT Male
Water filter(dual gradient)
µm
25
-
1
µm
polypropylene
(
1
): The minimum supply flow is required to the pump at the minimum supply pressure to meet the positive displacement
pump characteristics. The minimum supply flow is approximately 25% more than the nominal rated pump flow. The flow
rate and pressure can be greatly reduced by other processes, which need to be considered during and after installation.
(
2
) Standard hydraulic connections are NPT; G” connections (BSPP) are available on request
Tab 5.b
Tab 5.a
Summary of Contents for humiFog UA1K0HM00
Page 1: ...humiFog UA pressure atomizing 1000 5000 kg hr READ AND SAVE THESE INSTRUCTIONS ...
Page 33: ...34 of 55 Fig 11 a 11 4 1 Replacement parts for the hydraulics and drive assembly ...
Page 34: ...35 of 55 Replacement parts for the electrical panel Fig 11 b ...
Page 38: ...39 of 55 FOR PUMPING STATIONS UA1K8H 000 UA2K5H 000 for voltage 66 SERIES TSF BRASS ...
Page 39: ...40 of 55 FOR PUMPING STATIONS UA1K0H 001 UA1K8H 001 UA2K5H 001 for voltage 66 SERIES TSF SS ...
Page 40: ...41 of 55 FOR PUMPING STATIONS UA3K5H 000 UA5K0H 000 for voltage Emperor HT Brass ...
Page 41: ...42 of 55 FOR PUMPING STATIONS UA3K5H 001 UA5K0H 001 for voltage PARTS LIST KEZ36A ...
Page 44: ...45 of 55 11 6 Wiring Schematic Figure 11 c ...
Page 52: ...53 of 55 NOTES ...
Page 53: ...54 of 55 NOTES ...