31 of 55
10. Trouble-Shooting
The identification and solution of the problem may vary depending on the version of the software: Section 8.12 “Service ” explains how
to display the version of the software.
PROBLEM POSSIBLE
CAUSES
CHECKING
PROCEDURE
SOLUTION
No power supply (controller
doesn't start).
Incorrect power supply or fuses
on the transformer primary
blown.
Use a voltage tester and check the power
supply at the terminals on the terminal
block. Refer to the wiring diagram
Correct power supply. Replace any
blown fuses. See the wiring diagram
Fuse on transformer low
voltage side blown
Use a tester to check the electrical
continuity at the ends of the fuse.
Replace the fuse.
Transformer defective.
Use a tester to check for 24 volts at the
secondary
Replace the transformer
Controller or board defective
Use a tester to check the correct power
supply to the board and the controller.
Replace controller and board
Is the main switch on?
Check the position of the main switch
Turn the knob on the main switch
located on the door of the electrical
panel
No atomization at all or
insufficient atomization
Is the remote ON-OFF contact
closed?
Check the connection (or presence of
jumper) at correct wire terminals
Connect appropriate terminals to the
remote contact, if not jumper the two
terminals.
Check control algorithm.
Refer to control type menu
Set correct control parameter type
No supply water
Check for LP alarm on the controller
display
Check the water supply upstream and
downstream of the filters and restore
the water supply
Low supply water pressure
Calibrate the pressure of the supply
water to the correct limits
Water filter blocked
Check the pressure measured by the
pressure gauges upstream and
downstream of the water filters
Replace the dual gradient water filter
Water leaks from the rack or
the connection circuit between
humiFog and rack.
Repair the causes of any water leaks.
Low discharge pressure
replace the worn seals and valves on
the pump: (see the spare parts section
or pump manual)
Activation of VFD protection
Alarm “VFD Fault”
Check VFD configuration
Alarm EP, VFD on and high motor
temperature
Electric motor overload
Nozzles blocked
Nozzles do not atomize or atomize
incorrectly
Clean the nozzles
Alarms “Low Inlet Pressure”
Check the quality of the supply water
Capacity control solenoid
valves blocked
Incorrect electrical connection
Connect the power supply of the
solenoid valve correctly (see wiring
diagram)
Solenoid valve position not vertical
Reposition the solenoid valve correctly
Some nozzles do not
atomize correctly
Some capacity control solenoid
valves not open
Position of solenoid valve not correctly
vertical
Reposition the solenoid valve
Too many nozzles for the flow-
rate of the pump
With maximum production demand some
solenoid valves do not open
Choose a larger pump or decrease the
number of nozzles
Droplets atomized by the
nozzles too large
Low pressure.
Check the pressure displayed by the
pressure gauge. This must be
approximately between 860-1200 psi (60-
75 bar).
Adjust the pressure using the cap on
the high pressure regulator
Too many nozzles for the flow-
rate of the pump
Check the flow-rate of the pump and the
distribution system installed
Decrease the number of nozzles;
choose a pump with a higher flow-rate
High pressure alarm
Some lines downstream of the
pump are choked/blocked
Check the pressure on the pressure gauge
located on the pump
Restore the discharge circuit, high
pressure side, freeing the circuit from
any obstructions.
Continuous discharge of
water by the thermal valve
Water temperature in the
bypass above 135°F
Check that there are no blockages
downstream of the pump
Restore the discharge circuit, high
pressure side, freeing the circuit from
any obstructions.
Tab 10.a
Summary of Contents for humiFog UA1K0HM00
Page 1: ...humiFog UA pressure atomizing 1000 5000 kg hr READ AND SAVE THESE INSTRUCTIONS ...
Page 33: ...34 of 55 Fig 11 a 11 4 1 Replacement parts for the hydraulics and drive assembly ...
Page 34: ...35 of 55 Replacement parts for the electrical panel Fig 11 b ...
Page 38: ...39 of 55 FOR PUMPING STATIONS UA1K8H 000 UA2K5H 000 for voltage 66 SERIES TSF BRASS ...
Page 39: ...40 of 55 FOR PUMPING STATIONS UA1K0H 001 UA1K8H 001 UA2K5H 001 for voltage 66 SERIES TSF SS ...
Page 40: ...41 of 55 FOR PUMPING STATIONS UA3K5H 000 UA5K0H 000 for voltage Emperor HT Brass ...
Page 41: ...42 of 55 FOR PUMPING STATIONS UA3K5H 001 UA5K0H 001 for voltage PARTS LIST KEZ36A ...
Page 44: ...45 of 55 11 6 Wiring Schematic Figure 11 c ...
Page 52: ...53 of 55 NOTES ...
Page 53: ...54 of 55 NOTES ...