34
l
Can BREE
ZE
Operating and Maintenance Cooling Unit Instructions 8-14 kW
www.canovate.com
l
l
P. +90 216 484 2222
Fix Unit to the wall
1.
-
2. Ensure the foundation so that avoid
the deforming and noise.
3. In case of prevention from vibration
transfer to the building, use rubber
Mat.
Rubber Material
(Field Supplied)
Mark
Dimension
Model
7-14 kW
A (mm)
529
Suspended unit
1. Suspend the unit as the drawing
indicates.
2. Ensure that wall can resist the Out-
-
cation label plate.
3. It is recommended to select each foot
support to bear the full weight of
the unit (in order to consider stress
fatigue applied when unit is working
too).
Wall bracket (*)
Anchor Bolts (*)
(*) Field supplied
CAUTION
Pay attention to the following for installation:
Installation shall ensure that outdoor
unit will not incline, vibrate, make noise
or fall down by a blast of wind or in an
earthquake. Calculate quake-resistance
strength to ensure that installation is
strong enough against falling. Fix the unit
in a location without walls or windbreak
and likely exposed to a blast of wind.
to the front and back.
Installing location where the unit will be exposed to strong wind.
Follow the instructions below to install
on the rooftop or a location without sur-
rounding buildings, where strong wind is
expected against the product.
1. Choose a location where the outlet or
inlet side of the product will not be
exposed to strong wind.
2. When the outlet is exposed to strong
wind:
Direct strong wind may cause lack
operation.
CAUTION
Excessive strong wind against the outdoor unit
outlet may cause inverse rotation and damage
the fan and motor.
18. REFRIGERANT PIPING &
REFRIGERANT CHARGE
18.1 PIPING
MATERIALS
1
Prepare locally-supplied copper pipes.
2
Select the piping size with the correct thickness
and correct material which can have suf
fi
cient
pressure strength.
3
Select clean copper pipes. Make sure there is
no dust and moisture inside. Blow the inside of the
pipes with oxygen free nitrogen to remove any dust
and foreign materials before con- necting pipes.
N O T E
A system with no moisture or oil contamination will
give maximum performance and lifecycle compared