Operating and Maintenance Cooling Unit Instructions 8-14 kW
www.canovate.com
l
l
P. +90 216 484 2222
Drain Hose
Insulation
(field su pplied)
Secure
Downward
Slope
Clamp
Insulation
6. Do not connect the drain pipe with sanitary sewage
or any other drainage pipe.
7. When installing the pipe, do not tie the drain pipe
and refrigerant pipe together. Tie the drain pipe as
shown below
Band
Band
Rear Side piping
Rear Side piping
8. After completing the drain pipe work, pour water
into the drain pan and check to ensure that water
fl
ows smoothly
9. ELECTRICAL
WIRING
9.1
ELECTRICAL WIRING CONNECTION
FOR INDOOR UNIT
CAUTION:
Use twisted shielded pair cable or shield pair cable
for transmission wires between the indoor and the
outdoor units, and connect the shielded part to the
earth screw in the electrical box of the indoor unit as
shown below.
Single phase connection
Remote Control (PC-ART)
Transmission Wires
Power supply wires
(Single phase)
Earth Screw