www.canovate.com
l
l
P. +90 216 484 2222
Can BREE
ZE
Operating and Maintenance Cooling Unit Instructions 8-14 kW
l
9
great care to prevent damage.
• Do not lift the module any higher than 6” (152mm)
while moving it. If it must be lifted higher than 6”
(152mm), exercise great care and keep all personnel
who are not helping move the module at least 20’
(5m) away from the module.
• The Front Cooler ships with four outrigger-style
wheels to permit rolling it into position. Canovate
recommends using a forklift or pallet jack to move the
Front Cooler as near as practical to its installation site
before removing it from the shipping pallet.
4.3
Unpacking
Upon arrival of the module and before unpacking,
verify that the labeled equipment matches the bill of
lading. Carefully inspect all items for either visible or
concealed damage. Damage should be immediately
reported to the carrier and a damage claim
fi
led with a
copy sent to Canovate or to your sales representative.
If you later
fi
nd any concealed damage, report it to
both the shipping company and your local Canovate
representative.
Check to be sure all required assemblies and parts
have been received.
The Front Cooler is shipped in protective packaging
and secured to a pallet (see Figure 5). Do not remove
these protective items from the Front Cooler before
it is at the installation location. When unpacking and
handling the Front Cooler, exercise extra care to
prevent damage.
Caution
Risk of sudden refrigerant discharge. Can cause loss
of charge and minor injury.
If the optional pre-charged option is chosen, the
Front Cooler module is shipped with a full charge of
R-134a refrigerant under pressure. Do not remove
the pipe caps or plugs before the module is ready for
connection to Front Cooler Piping.
Supply and return
fi
ttings on the pre-charged Front
Cooler modules are one-shot couplings.
Do not disconnect one-shot couplings after they
have been connected. Disconnection will release
pressurized R-134a refrigerant from the Front Cooler.
Recyclable Packaging
All material used to package this module is recyclable.
Please save for future use or dispose of the material
appropriately.
WARNING :
Risk of top-heavy module falling over.
Can cause equipment damage, injury and death.
Read all of the following instructions before attempting
to move, lift, remove packaging from the module, or