8
2.2.4
Sidewall Clearance Specifications
Direct Vent Terminal Clearances
Canadian Installations
1
US Installations
2
A
Clearance above grade, veranda, porch, deck, or balcony
12” (30 cm)
12” (30 cm)
B
Clearance to window or door that may be opened
12” (15 cm) for appliances
<100,000 Btuh (30kW)
36” (91cm) for appliances
>100,000 Btuh (30kW)
9” (23 cm) for appliances <50,000
Btuh (15kW)
12” (30cm) for appliances
>50,000 Btuh (15kW)
C
Clearance to window or door that may be opened
-
-
D
Clearance to permanently closed window
-
-
E
Clearance to unventilated soffit
-
-
F
Clearance to outside corner
-
-
G
Clearance to inside corner
-
-
H
Clearance to each side of center line extended above
meter/regulator assembly
3’ (91 cm) within a height of 15’
(4.5 m) above the meter/ regulator
assembly
-
I
Clearance to service regulator vent outlet
36” (91 cm)
-
J
Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance
12” (15 cm) for appliances
<100,000 Btuh (30kW)
36” (91cm) for appliances
>100,000 Btuh (30kW)
9” (23 cm) for appliances <50,000
Btuh (15kW)
12” (30cm) for appliances
>50,000 Btuh (15kW)
K
Clearance to a mechanical air supply inlet
6’ (1.83 m)
3’ (91 cm) above if within 10’ (3
m) horizontally
L
Clearance above paved sidewalk or paved driveway located on
public property
7’ (2.13 m)
α
-
M
Clearance under veranda, porch deck, or balcony
12” (30 cm)
β
-
1
In accordance with the current CSA B149.1-15 and CSA B149.2-15 Natural Gas and Propane Installation Code
2
In accordance with ANSI Z223.1/ NFPA 54 National Fuel Gas Code
α
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both
dwellings
β
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/ NFPA 54 or CSA B149.1-15 and CSA B149.2-15. Clearance in accordance with local installation
codes and the requirements of the gas supplier
Summary of Contents for Valiant-FT II Series
Page 2: ...99 0419 Rev 00...
Page 40: ...36 PART 9 PIPING DIAGRAMS Figure 40 Single Boiler Hydronic Heating Zoned Piping...
Page 41: ...37 Figure 41 Multiple Boiler Hydronic Heating Zoned Piping...
Page 42: ...38 Figure 42 Single Boiler with DHW Tank Hydronic Heating Zoned Piping...
Page 43: ...39 PART 10 PARTS LIST...
Page 44: ...40...
Page 45: ...41...
Page 46: ...42...
Page 47: ...43...
Page 48: ...44...
Page 49: ...45...
Page 50: ...46...
Page 51: ...47...
Page 52: ...48...
Page 53: ...49...
Page 54: ...50...
Page 60: ...56 PART 11 TUBING DIAGRAM...
Page 61: ...57 PART 12 WIRING DIAGRAM...
Page 62: ...58...
Page 63: ...59...