17
3. Remove the bracket holding the airbox.
4. Remove the air intake elbow from the venturi.
5. Using a torx driver, remove the screws attaching
the venturi to the blower.
6. Replace this Venturi with the LP Venturi.
7. Follow steps 5 to 1 in reverse order to reattach all
the components.
8. Adjust high fire and low fire CO2 values using the
high fire and low fire trims on the gas valve and
match with table 12.
4.6
HIGH ALTITUDE
For US: The input ratings of the appliance operating at
elevations above 2000ft shall be reduced at the rate of 4%
for each 1000ft above sea level.
For Canada: The de-rated input rating above 2000ft is as
stated on the rating plate of the appliance. For operation
above 4500ft, consult the local authorities for de-rating
capacities.
AIR SWITCH PROCEDURE
1. Connect a manometer to the two air pressure
ports and check the differential pressure between
them.
2. Compare the pressures from the air switch to the
Valiant-FT Factory Test Data Sheet.
3. Match or come close to the required pressure by
changing the RPM on the digital display
Summary of Contents for Valiant-FT II Series
Page 2: ...99 0419 Rev 00...
Page 40: ...36 PART 9 PIPING DIAGRAMS Figure 40 Single Boiler Hydronic Heating Zoned Piping...
Page 41: ...37 Figure 41 Multiple Boiler Hydronic Heating Zoned Piping...
Page 42: ...38 Figure 42 Single Boiler with DHW Tank Hydronic Heating Zoned Piping...
Page 43: ...39 PART 10 PARTS LIST...
Page 44: ...40...
Page 45: ...41...
Page 46: ...42...
Page 47: ...43...
Page 48: ...44...
Page 49: ...45...
Page 50: ...46...
Page 51: ...47...
Page 52: ...48...
Page 53: ...49...
Page 54: ...50...
Page 60: ...56 PART 11 TUBING DIAGRAM...
Page 61: ...57 PART 12 WIRING DIAGRAM...
Page 62: ...58...
Page 63: ...59...