4
2.2.1
Venting Materials
Table 3: Venting Materials for Valiant-FT Series II
Material
Maximum Flue Temp (°F)
PVC
149
CPV
194
PPE
230
AL29-4C
300+, limited only by rating of seals
316L Stainless Steel
300+, limited only by rating of seals
*Use PVC, CPVC (only ULC-S636 approved plastic
material must be used in Canada) or AL29-4C gas vent
pipes listed for use with Category IV appliances. All venting
installations shall be in accordance with “Venting of
Equipment,” of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or “Venting Systems and Air Supply for
Appliances,” of the Natural Gas and Propane Installation
Code, CAN/ CSA B149.1, or applicable provisions of the
local building codes. Vent connectors serving appliances
vented by natural draft shall not be connected into any
portion of mechanical draft systems operating under
positive pressure. Use of cellular core PVC (ASTM F891),
cellular core CPVC, or Radel® (polyphenolsulfone) in
venting systems is prohibited. Covering non-metallic vent
pipe and fittings with thermal insulation shall be prohibited.
The horizontal venting run should be sloping upwards not
less than ¼ in/ft (21 mm/m) from the boiler to the vent
terminal. The venting system should be installed to prevent
accumulation of condensate and where necessary have the
means provided for drainage of the condensate.
Failure to install an approved vent on the unit can result in
severe property damage, injury or death!
In the case, the combustion air is drawn from outdoors, i.e.
direct vented, there are two configurations.
1.) Vertically Direct Vented
2.) Horizontally Direct Vented
2.2.2
Vertically Direct Vented
Location of Vent Termination
1.
Total length of piping for venting must not exceed
limits stated in Table 4.
Table 4: Valiant-FT Series II Vent Length Limits
Models
Air Intake
Exhaust
VA400
– VA850
Up to 120’
Up to 120’
Figure 7: Vertical Vent Termination
2.
Vent piping must terminate in a 45° elbow if plastic
piping is used or an approved vent cap if using
metal venting.
Figure 8: Vertically Direct Vented Clearances
3.
Vent outlet must be at least 1 foot away and 1 foot
above from the air inlet opening which must
terminate in a double 90° elbow facing
downwards.
Summary of Contents for Valiant-FT II Series
Page 2: ...99 0419 Rev 00...
Page 40: ...36 PART 9 PIPING DIAGRAMS Figure 40 Single Boiler Hydronic Heating Zoned Piping...
Page 41: ...37 Figure 41 Multiple Boiler Hydronic Heating Zoned Piping...
Page 42: ...38 Figure 42 Single Boiler with DHW Tank Hydronic Heating Zoned Piping...
Page 43: ...39 PART 10 PARTS LIST...
Page 44: ...40...
Page 45: ...41...
Page 46: ...42...
Page 47: ...43...
Page 48: ...44...
Page 49: ...45...
Page 50: ...46...
Page 51: ...47...
Page 52: ...48...
Page 53: ...49...
Page 54: ...50...
Page 60: ...56 PART 11 TUBING DIAGRAM...
Page 61: ...57 PART 12 WIRING DIAGRAM...
Page 62: ...58...
Page 63: ...59...