35
Table 11: Lockout Codes
#
Description
1
Unconfigured safety data
2
Waiting for safety data verification
3-46, 58-60, 97-99, 143-148, 172-178 Internal Fault. Replace SOLA Controller
47
Flame rod to ground leakage
48
Static Flame
49
24VAC low/high
50
Modulation Fault
64
Fan speed not proved, ignition failure
67
Interlock Off, safety circuit is open
79
Heater Outlet high limit tripped
82
Stack limit tripped (PVC: 149
°
F, CPVC: 194
°
F, 250
°
F)
105
Flame detected out of sequence
106
Flame lost if Main Flame Establishing Period (MFEP)
107
Flame lost early in run
108
Flame lost in run
109, 110
Ignition failed
112
Pilot test flame timeout
113
Flame circuit timeout
137
Interlock failed to close, safety circuit is open
149
Flame detected
Figure 26: Lockout Condition (Lockout screen)
To eliminate the lockout error,
1. Press the red bar, as circled above
2. Press the [Lockouts] button
3. Press [Clear Lockout]
Figure 25: Lockout Condition (Home screen)
Summary of Contents for Avenger Series
Page 2: ......
Page 35: ...30 Figure 21 Recommended Piping with Reverse Return and Variable Primary Flow...
Page 84: ...79 Figure B BLOWER BURNER ASSEMBLY...
Page 87: ...82 Figure C TYPICAL GAS TRAIN AR1000 AR3000 Figure D TYPICAL GAS TRAIN AR3500 AR4000...
Page 89: ...84 Figure E CONTROL BOARD ASSEMBLY...
Page 92: ...87 PART 13 ELECTRICAL DIAGRAMS...
Page 93: ...88...
Page 94: ...89...
Page 95: ...90...
Page 96: ...91...
Page 97: ...92...
Page 98: ...93...
Page 99: ...94...
Page 100: ...95...
Page 101: ...96...
Page 102: ...97...
Page 103: ...98...
Page 104: ...99...
Page 105: ...100...
Page 106: ...101...