PART 6 CONTROL PANEL
6.1
APPLIANCE TEMPERATURE CONTROLLER
The appliance is provided with a control panel at the front. Operating controls are installed inside the control box and are accessible by
undoing the (2) slotted screws and swinging the door open. The diagnostic information center as well as the on/off switch and the
appliance temperature controls reside on the control box door. The ignition module, VFD, transformer and relays are mounted on the
internal panel.
Figur: Control Panel Front
The SOLA icons will appear in one of four colors indicating the boiler status:
Blue: Normal operation
Red:
Lockout Condition
Yellow: Holding Mode
Grey: Communication Error
The Boiler Temperature Controller for this appliance is the Honeywell SOLA. It initiates the local call for heat and sets the target return
(appliance inlet) water temperature. This controller offers a range of operation modes that provides set point as well as modulating control.
It provides the following:
•
Readings of inlet and outlet water temperatures as well as flame signal.
•
Operation as an auto reset limit.
•
Operation as a control for inlet water temperature, outlet temperature, system temperature.
•
ΔT heat exchanger protection algorithm
.
•
Available storage tank mounted sensor used in conjunction with inlet sensor.
•
Adjustable: target temp, inter-stage differential, on delay between stages, minimum on time per stage, minimum off time per
stage.
•
Display of run hours for maintenance purposes. Counter wraps around at 10000 hours.
•
Flame failure signal.
•
JST and Molex connectors for ease of service.
•
Error message display in text.
•
Manual override of boiler input rate for combustion.
•
Pump exercising feature runs pump 10 seconds every three days in the event of no pump operation.
Levels of access
Two levels of access to simplify the use of the boiler.
User
: Access to general boiler and display settings and adjustments to the central heating, domestic hot water, and lead lag setpoint.
Installer
: Access to all user parameters and allows for changes to additional boiler parameters to allow for ease of startup and
serviceability.
NOTE
Due to the sensitivity of the touchscreen controller, using a stylus is recommended for accuracy
Summary of Contents for Avenger Series
Page 2: ......
Page 35: ...30 Figure 21 Recommended Piping with Reverse Return and Variable Primary Flow...
Page 84: ...79 Figure B BLOWER BURNER ASSEMBLY...
Page 87: ...82 Figure C TYPICAL GAS TRAIN AR1000 AR3000 Figure D TYPICAL GAS TRAIN AR3500 AR4000...
Page 89: ...84 Figure E CONTROL BOARD ASSEMBLY...
Page 92: ...87 PART 13 ELECTRICAL DIAGRAMS...
Page 93: ...88...
Page 94: ...89...
Page 95: ...90...
Page 96: ...91...
Page 97: ...92...
Page 98: ...93...
Page 99: ...94...
Page 100: ...95...
Page 101: ...96...
Page 102: ...97...
Page 103: ...98...
Page 104: ...99...
Page 105: ...100...
Page 106: ...101...