1.10
INSTALLATION PROCEDURE AND LOCATION OF UNIT
Install this appliance in a clean, dry location with adequate air supply.
•
Do not locate this appliance in an area where it will be subject to freezing unless precautions are taken. Radiant losses from the
Avenger are minimal and should not be relied on to keep the appliance room warm.
•
The appliance should be located close to a floor drain in an area where leakage from the appliance or connections will not result
in damage to the adjacent area or to lower floors in the structure.
It is recommended that a suitable drain pan, adequately
drained, be installed under the unit
. Under no circumstances is the manufacturer to be held responsible for water damage in
connection with this unit, or any of its components.
•
If the appliance is installed above the level of the buildings radiation system, a Low Water Cut-Off device must be installed above
the heat exchanger inlet/outlet connections. Some local codes require the installation of a low water cut-off on all systems.
•
When placing the appliance be aware that a minimum clearance of 24” must be provided at the front to allow easy access to the
heat exchanger.
•
The appliance must be installed so that the ignition system components are protected from water (dripping, spraying, etc.) during
appliance operation and service (circulator replacement, control replacement, etc.)
•
Appliances located in a residential garage or in adjacent spaces that open to the garage and are not part of the living space of
a dwelling unit, must be installed so that all burners and burner ignition devices have a minimum clearance of not less than 18”
(46 cm) above the floor. The appliance must be located or protected so that it is not subject to physical damage by a moving
vehicle.
•
DO NOT install this appliance in any location where gasoline or flammable vapors are likely to be present.
•
Appliance must be installed on a level floor
. Maintain required clearances from combustible surfaces.
•
Indoor models must be installed indoors where it is protected from exposure to wind, rain and weather.
•
Outdoor models must be installed outdoors. For outdoor installations, always consider the use of a shelter such as a garden
shed to prevent direct exposure of the appliance. The additional protection afforded by the shelter will help to minimize nuisance
problems with electrical connections and will allow easier servicing of the appliance under severe weather conditions.
Summary of Contents for Avenger Series
Page 2: ......
Page 35: ...30 Figure 21 Recommended Piping with Reverse Return and Variable Primary Flow...
Page 84: ...79 Figure B BLOWER BURNER ASSEMBLY...
Page 87: ...82 Figure C TYPICAL GAS TRAIN AR1000 AR3000 Figure D TYPICAL GAS TRAIN AR3500 AR4000...
Page 89: ...84 Figure E CONTROL BOARD ASSEMBLY...
Page 92: ...87 PART 13 ELECTRICAL DIAGRAMS...
Page 93: ...88...
Page 94: ...89...
Page 95: ...90...
Page 96: ...91...
Page 97: ...92...
Page 98: ...93...
Page 99: ...94...
Page 100: ...95...
Page 101: ...96...
Page 102: ...97...
Page 103: ...98...
Page 104: ...99...
Page 105: ...100...
Page 106: ...101...