CS616 and CS625 Water Content Reflectometers
;{CR10X}
;
*Table 1 Program
01: 300
Execution
Interval
(seconds)
1: Do (P86)
;Enable/Turn On the CS616 probe.
1: 41
Set
Port
1
High
2: Period Average (SE) (P27)
1: 1
Reps
2: 4
200 kHz Max Freq @ 2 V Peak to Peak, Period Output
3: 1
SE
Channel
4: 100
No.
of
Cycles
5: 1
Timeout
(0.01
sec
units)
6: 1
Loc [ period ]
7: 1.0
Mult
8: 0.0
Offset
3: Polynomial (P55)
1: 1
Reps
2: 1
X Loc [ period ]
3: 2
F(X) Loc [ vwc ]
4: -0.0663 C0
5: -0.0063 C1
6: 0.0007 C2
7: 0.0
C3
8: 0.0
C4
9: 0.0
C5
4: Do (P86)
;Turn Off CS616 probe
1: 51
Set
Port
1
Low
5: If time is (P92)
;Turn On Data Storage every hour
1: 0
Minutes (Seconds --) into a
2: 60
Interval (same units as above)
3: 10
Set Output Flag High (Flag 0)
6: Real Time (P77)
;Store a time stamp.
1: 1220
Year,Day,Hour/Minute
(midnight
=
2400)
7: Average (P71)
;Store the average VWC.
1: 1
Reps
2: 2
Loc [ vwc ]
*Table 2 Program
02: 0.0000 Execution
Interval
(seconds)
*Table 3 Subroutines
End Program
-Input Locations-
1 period 1 1 1
2 vwc 1 1 1
19
Summary of Contents for CS616
Page 2: ......
Page 8: ...Table of Contents iv ...
Page 50: ...CS616 and CS625 Water Content Reflectometers 42 ...
Page 52: ...Appendix A Discussion of Soil Water Content A 2 ...
Page 53: ......