CS616 and CS625 Water Content Reflectometers
9: CS616 Water Content Reflectometer (P138)
;Measure Period on 3ea CS616
1: 3
Reps
2: 1
SE
Channel
3: 13
All
reps
use
C3
4: 3
-- Loc [ Period_1 ]
5: 1.0
Mult
6: 0.0
Offset
;Note: Input "Loc" must be indexed "--" in a loop! How? Use the "F4" Key.
10: End (P95) ;end of loop
11: Do (P86)
;Set user flag 1 low
1: 21
Set
Flag
1
Low
12: End (P95)
;Do Loop End instruction
13: Do (P86)
;Set control port 1 "low" (i.e. Multiplexer Reset)
1: 51
Set
Port
1
Low
14: Polynomial (P55)
;Convert 48ea Period measurements into water content
1: 48
Reps
2: 3
X Loc [ Period_1 ]
3: 52
F(X) Loc [ VWC_1 ]
4: -0.0663 C0
5: -0.0063 C1
6: 0.0007 C2
7: 0.0
C3
8: 0.0
C4
9: 0.0
C5
15: If time is (P92)
;Store hourly averages every 4 hours
1: 0
Minutes (Seconds --) into a
2: 240
Interval (same units as above)
3: 10
Set Output Flag High (Flag 0)
16: Real Time (P77)
;Data Storage time stamp
1: 1220
Year,Day,Hour/Minute
(midnight
=
2400)
17: Average (P71)
;Data Storage Average, Location 1 & 2
1: 2
Reps
2: 1
Loc [ Bat_Volt ]
18: Average (P71)
;Data Storage Average, Location 52,53,..99
1: 48
Reps
2: 52
Loc [ VWC_1 ]
*Table 2 Program
02: 0.0000 Execution
Interval
(seconds)
*Table 3 Subroutines
End Program
25
Summary of Contents for CS616
Page 2: ......
Page 8: ...Table of Contents iv ...
Page 50: ...CS616 and CS625 Water Content Reflectometers 42 ...
Page 52: ...Appendix A Discussion of Soil Water Content A 2 ...