CS616 and CS625 Water Content Reflectometers
2: CS616 Water Content Reflectometer (P138)
1: 1
Reps
2: 1
SE
Channel
3: 1
C1 is first of sequential Control Ports used
4: 1
Loc [ period ]
5: 1.0
Mult
6: 0.0
Offset
3: Polynomial (P55)
1: 1
Reps
2: 1
X Loc [ period ]
3: 2
F(X) Loc [ VWC ]
4: -0.0663 C0
5: -0.0063 C1
6: 0.0007 C2
7: 0.0
C3
8: 0.0
C4
9: 0.0
C5
4: Do (P86)
1: 21
Set
Flag
1
Low
5: End (P95)
*Table 2 Program
02: 0.0000 Execution
Interval
(seconds)
*Table 3 Subroutines
End Program
-Input Locations-
1 period 1 0 1
2 VWC 1 0 1
6.4.5.2 CS616 Sample Edlog Program 2
Every 5 minutes, measure CS616 output period using instruction 27 and
convert to volumetric water content. Write hourly average to datalogger final
storage.
CS616
CR10X
green
Single-Ended Channel 1 (SE1)
orange
Control Port 1 (C1)
The red lead is connected to 12 Vdc and the black and shield are connected to
ground.
18
Summary of Contents for CS616
Page 2: ......
Page 8: ...Table of Contents iv ...
Page 50: ...CS616 and CS625 Water Content Reflectometers 42 ...
Page 52: ...Appendix A Discussion of Soil Water Content A 2 ...
Page 53: ......