AVW200-series 2-Channel Vibrating Wire Spectrum Analyzer Modules
3.2 Multiplexers Controlled by AVW200
3.2.1 Direct RS-232 Connection
Cable that Comes with Sensor
CABLE4CBL-L
Four
Conductor
Cable
17855 Pigtailed Cable or
18663
Null
Modem
Cable
19246
Power
Cable
Multiplexer
AVW200
Multiplexer
Datalogger
Power
Supply
Sensors
Sensors
For this example configuration, vibrating wire sensors are attached to
multiplexers, which are controlled by the AVW200. The AVW200 is
connected directly with the datalogger.
The following steps are used:
1.
If you are not using the default multiplexer, go to the
Deployment/Measurement tab in DevConfig and select the multiplexer
you are using (Section 5.1 and 5.2.1). The default multiplexer for the
AVW200 is the AM16/32A.
2.
Attach the multiplexers to the AVW200 as shown in Figure 4.5.1-1.
3.
Connect the sensors to the multiplexers.
Read more! Information about connecting the vibrating wire sensors to
the multiplexer is provided in the AM16/32B manual.
4.
Use the 17855 cable to attach the AVW200 to control port pairs on the
datalogger, or use the 18663 Null Modem cable to attach the AVW200 to
the RS-232 port on the datalogger.
5.
Connect one end of the 19246 power cable to the 12V and G terminals on
the AVW200 and the other end to the 12V and G terminals on the
datalogger or external power supply.
Read more! You can find power and ground connection information in
Section 4.2, and datalogger connection information in Section 4.3.
6.
Create a CRBasic program that includes the AVW200() instruction for
each of the multiplexers that the AVW200 will control.
14
Summary of Contents for AVW200 series
Page 2: ......
Page 78: ...Appendix C Antennas Antenna Cables and Surge Protectors for the AVW206 AVW211 and AVW216 C 8...
Page 86: ...Appendix E Status Table E 4...
Page 104: ...Appendix H Additional Programming Examples H 12...
Page 110: ...Appendix I Using MD485 Multidrop Modems with AVW200 Interfaces I 6...
Page 111: ......