FIGURE 4.1-1. Wiring for Sensor Connections
4.2 Power and Ground
Each AVW200 has a ground lug for connection to earth ground and a green
connector for attachment to a power source (see Figure 4.2-1).
Only connect the AVW200 ground lug to earth ground when the
AVW200 is not directly connected to the datalogger. When a
datalogger is in the same enclosure, only connect the
datalogger’s ground lug to earth ground.
NOTE
The AVW200’s ground lug is connected to earth ground via an 8 AWG wire.
This connection should be as short as possible.
The 19246 power cable is shipped with each AVW200 for connection to a
power source. The cable terminates in pigtails that attach to the 12V and G
terminals on the AVW200 and the power source. Often the AVW200 is
powered by the datalogger, but another 12 Vdc power source may be used.